Johnson Controls Unitary Products 43
115°F 125°F
6000
77 193.7 16.1 193.7 193.7 193.7 - - - 154.3 15.2 154.3 154.3 154.3 - - -
72 205.5 19.1 205.5 205.5 190.9 168.2 - - 182.9 19.8 182.9 182.9 182.9 182.9 - -
67 217.3 22.1 190.7 167.9 145.1 122.3 99.5 - 211.5 24.5 188.1 165.4 142.6 119.9 97.2 -
62 200.0 21.7 200.0 200.0 189.6 166.9 144.1 121.3 194.0 24.1 194.0 194.0 192.8 170.1 147.3 124.6
57 183.4 21.4 183.4 183.4 183.4 160.6 137.8 115.1 169.1 23.7 169.1 169.1 169.1 159.4 136.7 114.0
7000
77 208.6 16.3 227.3 214.1 201.0 - - - 173.4 15.4 173.4 173.4 173.4 - - -
72 221.4 19.3 213.0 199.9 179.4 154.9 - - 203.6 20.1 203.6 203.6 203.6 183.0 - -
67 234.1 22.3 185.4 160.9 136.4 111.8 87.3 - 233.9 24.8 172.4 148.5 124.5 100.6 76.6 -
62 215.5 22.0 209.7 196.6 178.2 153.7 129.1 104.6 214.5 24.5 205.9 187.7 169.5 145.9 121.6 97.7
57 197.5 21.7 197.5 197.5 191.7 167.2 142.7 118.1 187.7 24.0 187.7 187.7 187.7 165.1 140.6 116.7
8000
77 223.6 16.5 260.9 234.6 208.3 - - - 192.5 15.7 192.5 192.5 192.5 - - -
72 237.2 19.6 220.5 194.2 167.9 141.6 - - 224.4 20.4 224.4 211.0 185.8 160.6 - -
67 250.9 22.6 180.2 153.9 127.6 101.3 75.0 - 256.3 25.2 156.8 131.6 106.4 81.2 56.1 -
62 230.9 22.3 219.4 193.1 166.8 140.5 114.2 87.9 235.1 24.8 217.9 178.4 146.3 121.8 95.9 70.8
57 211.7 22.0 211.7 211.7 200.1 173.8 147.5 121.2 206.4 24.4 206.4 206.4 194.8 170.7 144.5 119.3
9000
72 246.6 19.6 238.3 225.1 205.3 175.3 - - 234.7 20.5 234.7 234.7 234.7 208.5 - -
67 260.8 22.7 216.1 186.0 156.0 126.0 96.0 - 267.7 25.2 203.8 173.3 143.9 114.5 85.1 -
62 240.1 22.3 234.3 221.1 203.9 173.9 143.9 113.9 245.6 24.9 237.0 217.3 195.7 166.7 136.9 107.5
57 220.1 22.0 220.1 220.1 214.3 184.3 154.3 124.3 215.8 24.4 215.8 215.8 210.0 181.1 151.2 121.7
10000
72 256.0 19.6 256.0 256.0 242.8 209.0 - - 245.0 20.5 245.0 245.0 245.0 245.0 - -
67 270.8 22.7 251.9 218.2 184.5 150.7 117.0 - 279.2 25.3 250.9 215.1 181.5 147.8 114.1 -
62 249.2 22.4 249.2 249.2 241.1 207.4 173.7 139.9 256.2 24.9 256.2 256.2 245.2 211.6 177.9 144.2
57 228.5 22.1 228.5 228.5 228.5 194.8 161.0 127.3 225.1 24.4 225.1 225.1 225.1 191.5 157.8 124.2
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20YD / Two J10NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65