Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
52 Johnson Controls Unitary Products
115°F 125°F
3000
77 113.3 12.1 58.5 45.8 33.1 - - - 105.9 13.2 57.8 45.0 32.1 - - -
72 105.2 12.0 77.8 65.1 52.4 39.7 - - 97.3 13.2 76.1 63.2 50.4 37.6 - -
67 97.2 11.9 97.2 84.4 71.7 59.0 46.3 - 88.7 13.1 88.7 81.5 68.7 55.8 43.0 -
62 95.9 11.8 95.9 95.9 86.5 73.8 61.1 48.4 90.6 13.1 90.6 90.6 82.5 69.6 56.8 43.9
57 97.1 11.8 97.1 97.1 86.6 73.9 61.2 48.4 89.5 13.0 89.5 89.5 80.5 67.7 54.8 42.0
3500
77 118.7 12.2 71.3 50.8 36.2 - - - 111.3 13.4 72.9 49.8 35.2 - - -
72 110.2 12.1 86.5 72.0 57.4 42.8 - - 102.2 13.3 84.4 69.8 55.1 40.5 - -
67 101.8 12.0 101.8 93.1 78.5 64.0 49.4 - 93.2 13.2 93.2 89.8 75.1 60.4 45.8 -
62 100.4 11.9 100.4 100.4 94.8 80.2 65.6 51.0 95.2 13.2 95.2 95.2 90.2 75.6 60.9 46.2
57 101.8 12.0 101.8 101.8 94.8 80.3 65.7 51.1 94.0 13.2 94.0 94.0 88.1 73.7 58.8 44.1
4000
77 124.1 12.3 84.0 55.8 39.4 - - - 116.6 13.5 88.0 54.6 38.2 - - -
72 115.3 12.2 95.2 78.8 62.4 45.9 - - 107.1 13.4 92.8 76.3 59.9 43.4 - -
67 106.4 12.1 106.4 101.8 85.4 68.9 52.5 - 97.7 13.3 97.7 97.7 81.5 65.1 48.6 -
62 105.0 12.1 105.0 105.0 103.0 86.6 70.1 53.7 99.7 13.3 99.7 99.7 97.9 81.6 65.0 48.5
57 106.4 12.1 106.4 106.4 103.1 86.7 70.2 53.8 98.5 13.3 98.5 98.5 95.6 79.7 62.7 46.2
4500
72 116.3 12.1 102.8 85.0 67.2 49.4 - - 107.6 13.3 101.0 83.1 65.1 47.1 - -
67 107.3 12.0 107.3 105.0 92.0 74.2 56.4 - 98.1 13.3 98.1 98.1 88.7 70.7 52.7 -
62 105.9 12.0 105.9 105.9 104.9 87.1 69.3 51.5 100.2 13.2 100.2 100.2 99.3 81.4 63.3 45.4
57 107.3 12.0 107.3 107.3 105.7 87.9 70.1 52.3 98.9 13.2 98.9 98.9 97.5 79.8 61.5 43.6
5000
72 117.2 12.1 110.4 91.2 72.0 52.9 - - 108.1 13.3 108.1 89.8 70.3 50.8 - -
67 108.3 12.0 108.3 108.3 98.6 79.5 60.3 - 98.6 13.2 98.6 98.6 95.8 76.3 56.8 -
62 106.8 11.9 106.8 106.8 106.8 87.6 68.5 49.3 100.7 13.2 100.7 100.7 100.7 81.2 61.7 42.2
57 108.2 11.9 108.2 108.2 108.2 89.0 69.9 50.7 99.4 13.1 99.4 99.4 99.4 79.9 60.4 40.9
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10PC/J10NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65