Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
60 Johnson Controls Unitary Products
115°F 125°F
6000
77 244.4 23.6 120.7 96.0 71.4 - - - 224.0 25.9 115.4 90.7 65.9 - - -
72 222.6 23.2 155.5 130.8 106.2 81.5 - - 205.1 25.5 150.0 125.3 100.6 75.8 - -
67 200.8 22.8 190.3 165.6 140.9 116.3 91.6 - 186.2 25.1 184.7 159.9 135.2 110.5 85.7 -
62 190.4 22.5 190.4 190.4 177.2 152.5 127.8 103.2 177.6 24.8 177.6 177.6 171.3 146.5 121.8 97.1
57 198.8 22.8 198.8 195.2 170.5 145.8 121.2 96.5 187.8 25.1 187.8 183.9 159.2 134.4 109.7 85.0
7000
77 248.3 23.6 140.9 104.7 77.1 - - - 227.3 25.9 139.8 99.1 71.4 - - -
72 226.1 23.2 169.8 142.2 114.6 87.0 - - 208.1 25.5 164.3 136.6 108.9 81.3 - -
67 204.0 22.9 198.7 179.8 152.2 124.6 97.0 - 188.9 25.2 188.8 174.1 146.4 118.7 91.1 -
62 193.4 22.6 193.4 193.4 191.3 163.7 136.1 108.5 180.2 24.8 180.2 180.2 180.2 158.3 130.1 102.4
57 201.9 22.8 201.9 200.1 184.1 156.5 128.9 101.3 190.6 25.1 190.6 188.6 172.4 145.8 117.0 89.3
8000
77 252.1 23.7 161.2 113.3 82.7 - - - 230.6 26.0 164.3 107.6 76.9 - - -
72 229.6 23.3 184.1 153.6 123.1 92.5 - - 211.1 25.6 178.6 148.0 117.3 86.7 - -
67 207.1 22.9 207.1 194.0 163.4 132.9 102.4 - 191.7 25.2 191.7 188.3 157.7 127.0 96.4 -
62 196.4 22.6 196.4 196.4 205.4 174.9 144.4 113.8 182.8 24.9 182.8 182.8 182.8 170.1 138.4 107.8
57 205.1 22.9 205.1 205.1 197.7 167.2 136.6 106.1 193.3 25.2 193.3 193.3 185.7 157.2 124.4 93.7
9000
72 233.2 23.5 193.9 160.2 126.5 92.8 - - 214.2 25.8 188.4 154.6 120.8 87.0 - -
67 210.3 23.2 210.3 201.6 168.0 134.3 100.6 - 194.5 25.5 194.5 194.5 162.4 128.6 94.8 -
62 199.4 22.8 199.4 199.4 203.9 170.3 136.6 102.9 185.4 25.1 185.4 185.4 185.4 161.6 127.3 93.5
57 208.3 23.1 208.3 208.3 203.2 169.5 135.9 102.2 196.1 25.4 196.1 196.1 191.3 158.5 123.7 89.9
10000
72 236.7 23.8 203.6 166.8 129.9 93.1 - - 217.2 26.1 198.2 161.3 124.3 87.4 - -
67 213.5 23.4 213.5 209.3 172.5 135.7 98.9 - 197.2 25.7 197.2 197.2 167.1 130.2 93.2 -
62 202.5 23.1 202.5 202.5 202.5 165.6 128.8 92.0 188.1 25.4 188.1 188.1 188.1 153.1 116.1 79.2
57 211.4 23.4 211.4 211.4 208.7 171.9 135.1 98.3 198.9 25.7 198.9 198.9 196.8 159.9 123.0 86.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20PD/J20ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65