Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 19
115°F 125°F
2250
77 103.1 9.1 48.5 39.5 30.4 - - - 98.9 10.1 47.1 38.0 29.0 - - -
72 95.4 9.0 61.2 52.1 43.1 34.0 - - 91.6 9.9 59.8 50.7 41.7 32.6 - -
67 87.6 8.9 73.9 64.8 55.8 46.7 37.6 - 84.4 9.8 72.5 63.4 54.4 45.3 36.2 -
62 80.6 8.7 80.6 77.7 68.6 59.5 50.4 41.4 77.2 9.7 77.2 76.0 67.0 57.9 48.8 39.8
57 79.5 8.6 79.5 79.5 72.1 63.0 54.0 44.9 76.6 9.5 76.6 76.6 69.3 60.2 51.2 42.1
2625
77 106.1 9.2 52.6 42.4 32.2 - - - 102.1 10.2 51.2 41.0 30.8 - - -
72 98.2 9.1 66.0 55.9 45.7 35.5 - - 94.6 10.1 64.7 54.5 44.3 34.2 - -
67 90.3 9.0 79.5 69.3 59.1 49.0 38.8 - 87.1 9.9 78.2 68.0 57.8 47.7 37.5 -
62 83.0 8.8 83.0 81.5 72.8 62.6 52.4 42.3 79.7 9.8 79.7 79.3 71.2 61.2 50.9 40.7
57 81.8 8.7 81.8 81.8 76.5 66.3 56.2 46.0 79.0 9.6 79.0 79.0 73.7 63.8 53.4 43.2
3000
77 109.2 9.3 56.6 45.3 34.1 - - - 105.3 10.3 55.2 44.0 32.7 - - -
72 101.0 9.2 70.8 59.6 48.3 37.0 - - 97.5 10.2 69.5 58.3 47.0 35.7 - -
67 92.9 9.1 85.1 73.8 62.5 51.3 40.0 - 89.8 10.1 83.9 72.6 61.3 50.0 38.7 -
62 85.4 8.9 85.4 85.4 76.9 65.7 54.4 43.1 82.2 10.0 82.2 82.2 75.5 64.5 53.0 41.7
57 84.2 8.8 84.2 84.2 80.9 69.6 58.4 47.1 81.5 9.8 81.5 81.5 78.2 67.4 55.6 44.3
3375
72 103.1 9.2 75.2 62.9 50.7 38.4 - - 99.4 10.2 73.9 61.6 49.3 37.1 - -
67 94.7 9.1 90.1 77.8 65.6 53.3 41.1 - 91.5 10.1 88.9 76.6 64.4 52.1 39.8 -
62 87.1 9.0 87.1 87.1 80.7 68.4 56.2 43.9 83.7 10.0 83.7 83.7 79.3 67.2 54.7 42.5
57 85.9 8.8 85.9 85.9 84.2 72.0 59.7 47.5 83.0 9.8 83.0 83.0 81.4 69.4 56.8 44.6
3750
72 105.1 9.2 79.5 66.2 53.0 39.8 - - 101.3 10.2 78.2 64.9 51.7 38.4 - -
67 96.6 9.1 95.1 81.9 68.6 55.4 42.1 - 93.2 10.1 93.2 80.7 67.4 54.2 40.9 -
62 88.8 9.0 88.8 88.8 84.4 71.2 57.9 44.7 85.3 10.0 85.3 85.3 83.1 69.8 56.5 43.3
57 87.6 8.8 87.6 87.6 87.6 74.3 61.1 47.8 84.6 9.8 84.6 84.6 84.6 71.3 58.1 44.8
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J07YC/J10NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65