Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
6 Johnson Controls Unitary Products
been mechanically expanded into aluminum fins. Both
headers are located on the same end of the coil. The coil is
leak-tested at 325 psig and dried before the connections are
capped for storage and shipping.
Guide Specifications
Split System Cooling Only Condensing Units
Models: J07 thru 25YC, J10 thru 20YD & Split
System Heat Pump Models: J07 thru 25PC, J15 thru
20PD
General
Factory assembled, single piece, air cooled condensing
unit designed for outdoor installation.
Factory wired, piped, and tested for leakage and
functionality to assure trouble-free installation and start-
up.
Rated in accordance with ARI Standard 340/360.
Manufactured in a facility registered under the ISO 9002
manufacturing quality standard.
Designed and tested in accordance with ASHRAE 15
Safety Code for Mechanical Refrigeration and comply
with NEC.
Cooling performance rated in accordance with DOE
and ARI test procedures.
CSA listed and classified to UL 1995/CAN/CSA No.
236- M90 standards.
One year limited parts warranty on complete unit with
an additional four year compressor warranty.
Unit Operating Characteristics
Operating Range shall be between 125° F to 40° F in cooling
as standard from factory.
The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of _____
F. The power consumption at full load shall not exceed
_____ kW.
The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling
capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator at
_____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____F.
The system shall have an EER of _____ Btuh/ Watt or
greater at standard ARI conditions.
Installer Shall
Furnish JCI® air-cooled condensing units, heat pump or
equivalent in accordance with the performance
schedule shown on the plans, and
Unit shall be stored and handled in accordance with unit
manufacturer's instructions.
Install each unit as shown on the plans in accordance
with the manufacturer’s recommendations and all
applicable national and local codes
Unit Construction
Constructed of zinc-coated, galvanized steel.
Exterior surfaces bonded and coated with baked
enamel finish by a powder paint process capable of
withstanding a minimum of 1000 salt spray hours
according to ASTM B117.
Cabinet screws that comply with ASTM B117 salt spray
test for a minimum of 750 hours.
Permanently attached heavy-gage perimeter base rails
with forklift slots and lifting holes.
Removable access panels to all internal components.
Separate access panel to controls.
Access panels to allow outdoor coil cleaning.
Compressor(s)
Hermetic scroll type, internally protected with high-
pressure relief and over temperature protection.
Two stage units operate in 50% capacity increments.
Suction gas cooled
Voltage range of ±10% of unit nameplate voltage.
Neoprene isolators minimize sound transmission and
vibration.
Belly-band crankcase heaters keep refrigerant from
diluting sump oil.
Full charge of compressor oil
Outdoor Condenser Unit Coils
Draw thru configuration
Constructed with Micro-channel aluminum fins and
aluminum tubing. All refrigerant tubing must share a
common header.
Heat Pump Unit Outdoor Unit Coils
Draw thru configuration
Constructed with aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
Condenser Fans
Direct driven propeller-type fans
Statically and dynamically balanced
Aluminum blades riveted to corrosion resistant steel
spider brackets.
Arranged for vertical air discharge.
Equipped with PVC coated steel wire safety guards.