Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 31
115°F 125°F
4500
77 203.2 18.8 106.1 86.7 67.4 - - - 198.7 21.0 104.2 84.9 65.6 - - -
72 187.4 18.3 131.7 112.3 93.0 73.7 - - 182.9 20.3 129.8 110.4 91.1 71.8 - -
67 171.6 17.7 157.3 137.9 118.6 99.3 79.9 - 167.2 19.6 155.3 136.0 116.7 97.3 78.0 -
62 153.7 17.2 153.7 153.7 137.3 117.9 98.6 79.3 149.3 19.0 149.3 149.3 133.5 114.1 94.8 75.5
57 157.8 17.1 157.8 157.8 141.1 121.7 102.4 83.0 154.9 18.9 154.9 154.9 138.0 118.7 99.4 80.1
5250
77 208.6 19.0 117.7 94.1 72.1 - - - 204.0 21.1 116.8 92.2 70.3 - - -
72 192.4 18.4 143.4 121.4 99.5 77.6 - - 187.8 20.4 141.5 119.6 97.6 75.7 - -
67 176.2 17.8 169.0 148.8 126.9 105.0 83.0 - 171.7 19.7 166.2 146.9 125.0 103.0 81.1 -
62 157.8 17.3 157.8 157.8 146.9 124.9 103.0 81.1 153.3 19.1 153.3 153.3 143.0 121.2 99.1 77.2
57 162.0 17.2 162.0 162.0 150.9 129.0 107.0 85.1 159.1 19.0 159.1 159.1 147.9 126.3 104.0 82.1
6000
77 214.1 19.1 129.4 101.4 76.8 - - - 209.3 21.2 129.3 99.5 74.9 - - -
72 197.4 18.5 155.1 130.6 106.0 81.5 - - 192.8 20.5 153.2 128.7 104.1 79.6 - -
67 180.8 17.9 180.8 159.7 135.2 110.7 86.1 - 176.2 19.8 176.2 157.8 133.3 108.8 84.2 -
62 162.0 17.4 162.0 162.0 156.5 131.9 107.4 82.8 157.3 19.2 157.3 157.3 152.5 128.2 103.4 78.9
57 166.3 17.3 166.3 166.3 160.8 136.3 111.7 87.2 163.2 19.1 163.2 163.2 157.8 133.8 108.7 84.1
6750
72 200.5 18.5 165.1 138.2 111.4 84.5 - - 195.9 20.5 163.2 136.3 109.5 82.6 - -
67 183.6 17.9 183.6 168.9 142.0 115.2 88.3 - 179.1 19.7 179.1 167.0 140.2 113.3 86.5 -
62 164.5 17.4 164.5 164.5 161.7 134.9 108.0 81.2 159.9 19.2 159.9 159.9 157.5 130.8 103.8 77.0
57 168.8 17.3 168.8 168.8 166.1 139.3 112.4 85.6 165.9 19.0 165.9 165.9 163.2 136.7 109.5 82.7
7500
72 203.6 18.5 175.0 145.9 116.7 87.6 - - 199.1 20.4 173.1 144.0 114.9 85.7 - -
67 186.4 17.9 186.4 178.0 148.8 119.7 90.5 - 182.0 19.7 182.0 176.2 147.0 117.9 88.7 -
62 167.0 17.4 167.0 167.0 167.0 137.8 108.7 79.5 162.5 19.2 162.5 162.5 162.5 133.3 104.2 75.0
57 171.4 17.3 171.4 171.4 171.4 142.3 113.1 83.9 168.6 19.0 168.6 168.6 168.6 139.5 110.3 81.2
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YC/J20NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65