115°F 125°F
3000
77 116.8 12.1 58.7 46.2 33.7 - - - 111.5 13.3 57.0 44.4 31.8 - - -
72 106.7 11.9 75.9 63.4 50.9 38.4 - - 100.7 13.2 73.6 61.1 48.5 35.9 - -
67 96.6 11.8 93.2 80.7 68.2 55.7 43.2 - 89.9 13.1 89.9 77.7 65.1 52.6 40.0 -
62 89.7 11.7 89.7 89.7 83.3 70.8 58.3 45.8 84.4 12.9 84.4 84.4 80.0 67.5 54.9 42.3
57 93.0 11.7 93.0 92.9 80.4 67.9 55.4 42.9 87.9 12.9 87.9 87.9 75.5 62.9 50.3 37.8
3500
77 122.7 12.1 71.5 52.0 37.7 - - - 116.2 13.3 72.4 50.2 35.8 - - -
72 112.1 11.9 85.6 71.3 57.0 42.7 - - 105.0 13.2 83.3 68.9 54.5 40.1 - -
67 101.4 11.8 99.7 90.6 76.3 62.0 47.7 - 93.7 13.1 93.7 87.6 73.2 58.8 44.4 -
62 94.2 11.7 94.2 94.2 93.2 78.9 64.6 50.3 88.0 12.9 88.0 88.0 88.0 75.8 61.1 46.7
57 97.7 11.7 97.7 97.6 90.0 75.7 61.4 47.1 91.5 13.0 91.5 91.5 84.8 70.9 56.0 41.6
4000
77 128.6 12.1 84.3 57.8 41.7 - - - 120.9 13.3 87.7 56.0 39.7 - - -
72 117.4 11.9 95.3 79.2 63.1 46.9 - - 109.2 13.2 93.0 76.8 60.5 44.2 - -
67 106.3 11.8 106.3 100.5 84.4 68.3 52.2 - 97.4 13.1 97.4 97.4 81.3 65.0 48.8 -
62 98.8 11.7 98.8 98.8 103.1 87.0 70.9 54.8 91.5 12.9 91.5 91.5 91.5 84.2 67.3 51.1
57 102.3 11.7 102.3 102.3 99.6 83.5 67.3 51.2 95.2 13.0 95.2 95.2 94.2 78.8 61.7 45.4
4500
72 122.9 12.0 103.0 85.3 67.6 49.9 - - 114.7 13.2 100.8 82.9 65.0 47.0 - -
67 111.2 11.8 111.2 108.2 90.5 72.8 55.1 - 102.4 13.1 102.4 102.4 87.3 69.3 51.4 -
62 103.3 11.7 103.3 103.3 105.5 87.8 70.1 52.4 96.1 12.9 96.1 96.1 96.1 82.6 64.4 46.5
57 107.1 11.7 107.1 107.1 105.7 88.0 70.3 52.6 100.0 13.0 100.0 100.0 99.5 82.0 63.6 45.7
5000
72 128.3 12.0 110.8 91.5 72.2 52.9 - - 120.2 13.3 108.7 89.0 69.4 49.8 - -
67 116.1 11.9 116.1 115.9 96.6 77.3 58.0 - 107.3 13.2 107.3 107.3 93.3 73.7 54.1 -
62 107.9 11.7 107.9 107.9 107.9 88.6 69.3 50.0 100.7 13.0 100.7 100.7 100.7 81.1 61.5 41.9
57 111.8 11.8 111.8 111.8 111.8 92.5 73.2 53.9 104.8 13.0 104.8 104.8 104.8 85.2 65.6 46.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10YD/J10ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65