Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 41
115°F 125°F
6000
77 244.4 23.4 120.7 96.0 71.4 - - - 229.9 25.9 117.5 92.5 67.5 - - -
72 226.2 22.8 156.5 131.9 107.2 82.6 - - 212.8 25.1 153.2 128.2 103.2 78.1 - -
67 208.0 22.1 192.4 167.7 143.1 118.5 93.8 - 195.7 24.3 188.9 163.9 138.9 113.8 88.8 -
62 192.2 21.6 192.2 192.2 178.1 153.5 128.8 104.2 179.4 23.8 179.4 179.4 173.7 148.6 123.6 98.6
57 194.4 21.8 194.4 194.4 174.8 150.2 125.5 100.9 184.6 23.9 184.6 184.6 162.9 137.9 112.9 87.8
7000
77 250.0 23.5 136.5 104.5 76.9 - - - 235.5 25.9 135.8 101.0 72.8 - - -
72 231.4 22.8 170.8 143.1 115.5 87.9 - - 218.0 25.1 167.7 139.5 111.3 83.1 - -
67 212.8 22.1 205.0 181.7 154.1 126.5 98.9 - 200.5 24.3 199.6 178.0 149.8 121.6 93.4 -
62 196.7 21.7 196.7 196.7 191.8 164.2 136.5 108.9 183.8 23.8 183.8 183.8 183.8 159.9 130.9 102.7
57 198.9 21.8 198.9 198.9 188.3 160.6 133.0 105.4 189.1 24.0 189.1 189.1 175.8 148.8 119.4 91.2
8000
77 255.7 23.5 152.4 113.0 82.4 - - - 241.1 25.9 154.0 109.5 78.1 - - -
72 236.6 22.8 185.0 154.4 123.7 93.1 - - 223.2 25.1 182.1 150.8 119.4 88.0 - -
67 217.6 22.2 217.6 195.7 165.1 134.5 103.9 - 205.3 24.3 205.3 192.1 160.7 129.3 97.9 -
62 201.1 21.7 201.1 201.1 205.5 174.9 144.3 113.6 188.2 23.9 188.2 188.2 188.2 171.2 138.2 106.9
57 203.3 21.8 203.3 203.3 201.7 171.1 140.5 109.8 193.6 24.0 193.6 193.6 188.6 159.7 125.9 94.5
9000
72 241.9 23.0 195.9 162.8 129.7 96.5 - - 228.6 25.4 193.3 159.5 125.8 92.0 - -
67 222.4 22.3 222.4 206.1 173.0 139.9 106.8 - 210.3 24.6 210.3 203.0 169.3 135.5 101.7 -
62 205.6 21.9 205.6 205.6 207.8 174.6 141.5 108.4 192.7 24.1 192.7 192.7 192.7 167.4 132.8 99.0
57 207.9 22.0 207.9 207.9 207.0 173.9 140.8 107.7 198.3 24.2 198.3 198.3 195.8 163.2 128.2 94.4
10000
72 247.2 23.2 206.8 171.2 135.6 100.0 - - 233.9 25.6 204.5 168.3 132.1 95.9 - -
67 227.3 22.5 227.3 216.5 180.9 145.3 109.7 - 215.2 24.8 215.2 214.0 177.8 141.6 105.4 -
62 210.0 22.0 210.0 210.0 210.0 174.4 138.8 103.2 197.3 24.3 197.3 197.3 197.3 163.5 127.4 91.2
57 212.4 22.2 212.4 212.4 212.4 176.8 141.2 105.6 202.9 24.5 202.9 202.9 202.9 166.7 130.5 94.3
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20YC/J20NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65