Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 45
115°F 125°F
6000
77 249.8 22.6 126.1 101.0 75.8 - - - 236.8 24.9 122.5 97.3 72.0 - - -
72 229.9 22.3 160.6 135.4 110.3 85.1 - - 217.9 24.6 156.4 131.2 106.0 80.8 - -
67 210.1 22.0 195.1 169.9 144.8 119.6 94.4 - 199.0 24.3 190.3 165.1 139.9 114.7 89.5 -
62 198.2 21.9 198.2 198.2 178.3 153.1 128.0 102.8 187.8 24.3 187.8 187.8 170.7 145.5 120.3 95.1
57 196.0 21.9 196.0 196.0 176.5 151.3 126.1 101.0 187.0 24.2 187.0 187.0 166.7 141.5 116.3 91.1
7000
77 255.8 22.7 143.3 110.0 81.7 - - - 242.9 24.9 142.6 106.7 78.2 - - -
72 235.5 22.4 175.5 147.2 118.9 90.6 - - 223.6 24.7 172.0 143.5 115.0 86.6 - -
67 215.2 22.1 207.7 184.4 156.1 127.8 99.5 - 204.2 24.4 201.3 180.3 151.8 123.4 94.9 -
62 203.0 22.0 203.0 203.0 192.2 163.9 135.7 107.4 192.7 24.3 192.7 192.7 185.3 157.5 128.4 99.9
57 200.8 22.0 200.8 200.8 190.3 162.0 133.7 105.4 191.9 24.3 191.9 191.9 181.0 153.4 124.1 95.6
8000
77 261.9 22.8 160.5 119.1 87.7 - - - 249.1 25.0 162.8 116.1 84.4 - - -
72 241.1 22.5 190.4 159.0 127.5 96.1 - - 229.3 24.8 187.5 155.8 124.1 92.3 - -
67 220.3 22.2 220.3 198.8 167.4 136.0 104.6 - 209.4 24.5 209.4 195.5 163.8 132.0 100.3 -
62 207.8 22.1 207.8 207.8 206.2 174.8 143.3 111.9 197.6 24.4 197.6 197.6 197.6 169.4 136.4 104.7
57 205.5 22.1 205.5 205.5 204.1 172.7 141.3 109.8 196.7 24.4 196.7 196.7 195.3 165.3 131.8 100.1
9000
72 246.6 22.7 199.8 166.1 132.5 98.8 - - 234.9 25.0 196.6 162.8 129.0 95.2 - -
67 225.3 22.4 225.3 207.6 173.9 140.3 106.6 - 214.6 24.7 214.6 204.1 170.3 136.5 102.7 -
62 212.6 22.3 212.6 212.6 211.8 178.2 144.5 110.9 202.4 24.6 202.4 202.4 202.4 171.1 136.7 102.9
57 210.3 22.3 210.3 210.3 209.5 175.9 142.3 108.6 201.6 24.6 201.6 201.6 200.8 167.9 133.2 99.4
10000
72 252.2 23.0 209.2 173.3 137.4 101.6 - - 240.5 25.2 205.7 169.9 134.0 98.1 - -
67 230.4 22.7 230.4 216.3 180.4 144.6 108.7 - 219.7 24.9 219.7 212.7 176.8 141.0 105.1 -
62 217.4 22.5 217.4 217.4 217.4 181.5 145.7 109.8 207.3 24.8 207.3 207.3 207.3 172.8 136.9 101.0
57 215.0 22.5 215.0 215.0 215.0 179.1 143.3 107.4 206.4 24.8 206.4 206.4 206.4 170.5 134.7 98.8
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20YD/J20ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65