112 Johnson Controls Unitary Products
Unit Mounting - J25NC
The J25NC evaporator blower may be suspended from the
joists with isolation type hangers or hooks. Suspension
accessories 1HH0403 (J25NC) may be ordered separately.
All Suspension accessories include three suspension
channels and hardware. The channels extend across the
evaporator coil section, the heating coil section (if included)
and the blower section. Each channel is to be bolted to each
section as shown.
Typical Suspension of J25NC
AX
3
1-1/2
EVAP. COIL
SECTION
BLOWER
SECTION
U
3
O
U
HEATING COIL
2
SUSPENSION
ANGLES
1
BLOWER
SECTION
EVAP.
COIL
SECTION
CX
1
2
3
3
4
4
VERTICAL UNIT SUPPORTED
FROM BELOW
F
A
B
E
D
B
A
E
AX
BX
BX
BX
BX
HORIZONTAL
UNIT SUSPENDED
FROM ABOVE
The same channels can be used in either position. When used to
support a vertical unit, these channels should be cut to match the
bottom dimension of the evaporator section.
The suspension channels have two sets of mounting holes to
accommodate horizontal units with or without a heating coil. On
a horizontal unit without a heating coil, the suspension channels
will extend 3” beyond both ends of the unit.
The same channels can be used to support a horizontal, floor-
mounted unit from below.
After these bottom channels are cut per Note 1, a new hole will have
to be drilled at the cut end if the unit is to be mounted on isolators.
C
D
C
F
Unit Mounting Dimensions- J25NC
UNIT
DIMENSIONS, INCHES
AX BX CX
J25NC
69-1/4 49-1/16 26-5/8