Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 79
Electrical Data For Indoor Models
Electrical Data - Indoor Units
Motor HP Power Supply
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
FLA Model KW Stages Amps
J07NCC00B
1.5
208-3-60 5.0
None --- --- --- 6.3 15
10 KW 7.5 1 20.8 32.3 35
16 KW 12 2 33.4 47.9 50
26 KW 19.5 2 54.2 74.0 80
36 KW 27 2 75.1 100.1 110
230-3-60 5.2
None --- --- --- 6.5 15
10 KW 10 1 24.1 36.6 40
16 KW 16 2 38.5 54.6 60
26 KW 26 2 62.5 84.7 90
36 KW 36 2 86.6 114.8 125
460-3-60 2.5
None --- --- --- 3.1 15
10 KW 10 1 12.0 18.2 20
16 KW 16 2 19.2 27.2 30
26 KW 26 2 31.3 42.2 45
36 KW 36 2 43.3 57.3 60
575-3-60 2.0
None --- --- --- 2.5 15
10 KW 10 1 9.6 14.5 15
16 KW 16 2 15.4 21.7 25
26 KW 26 2 25.0 33.8 35
36 KW 36 2 34.6 45.8 50
J07NCC00C, J10NC/NDC00C
2.0
208-3-60 6.6
None --- --- --- 8.3 15
10 KW 7.5 1 20.8 34.3 35
16 KW 12 2 33.4 49.9 50
26 KW 19.5 2 54.2 76.0 80
36 KW 27 2 75.1 102.1 110
230-3-60 6.8
None --- --- --- 8.5 15
10 KW 10 1 24.1 38.6 40
16 KW 16 2 38.5 56.6 60
26 KW 26 2 62.5 86.7 90
36 KW 36 2 86.6 116.8 125
460-3-60 3.4
None --- --- --- 4.3 15
10 KW 10 1 12.0 19.3 20
16 KW 16 2 19.2 28.3 30
26 KW 26 2 31.3 43.3 45
36 KW 36 2 43.3 58.4 60
575-3-60 2.4
None --- --- --- 3.0 15
10 KW 10 1 9.6 15.0 20
16 KW 16 2 15.4 22.2 25
26 KW 26 2 25.0 34.3 35
36 KW 36 2 34.6 46.3 50