Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 33
115°F 125°F
4500
77 193.0 17.7 96.7 79.6 62.4 - - - 188.7 19.3 94.6 77.5 60.3 - - -
72 179.5 17.4 121.8 104.6 87.5 70.3 - - 175.3 19.0 119.9 102.7 85.5 68.3 - -
67 166.0 17.1 146.9 129.7 112.6 95.4 78.2 - 161.9 18.7 145.1 127.9 110.7 93.5 76.4 -
62 154.6 16.8 154.6 154.6 137.6 120.4 103.3 86.1 152.9 18.5 152.9 152.9 136.1 118.9 101.7 84.6
57 151.8 16.8 151.8 151.8 136.4 119.2 102.1 84.9 148.2 18.4 148.2 148.2 132.2 115.1 97.9 80.7
5250
77 198.9 17.8 105.2 86.0 66.7 - - - 193.8 19.4 103.0 83.7 64.5 - - -
72 185.0 17.5 132.0 112.8 93.6 74.3 - - 180.0 19.1 129.9 110.7 91.5 72.2 - -
67 171.0 17.2 158.9 139.6 120.4 101.2 81.9 - 166.2 18.8 156.9 137.7 118.4 99.2 80.0 -
62 159.2 16.9 159.2 159.2 147.2 128.0 108.7 89.5 157.1 18.6 157.1 157.1 145.6 126.6 107.1 87.9
57 156.4 16.9 156.4 156.4 145.9 126.7 107.5 88.2 152.2 18.5 152.2 152.2 141.4 122.6 103.0 83.7
6000
77 204.7 17.9 113.7 92.4 71.1 - - - 198.9 19.5 111.3 90.0 68.7 - - -
72 190.4 17.6 142.3 121.0 99.7 78.4 - - 184.8 19.2 140.0 118.7 97.4 76.1 - -
67 176.1 17.2 170.9 149.6 128.3 107.0 85.7 - 170.6 18.9 168.7 147.4 126.1 104.9 83.6 -
62 163.9 17.0 163.9 163.9 156.8 135.5 114.2 92.9 161.3 18.7 161.3 161.3 155.1 134.3 112.5 91.2
57 161.0 17.0 161.0 161.0 155.4 134.2 112.9 91.6 156.2 18.6 156.2 156.2 150.7 130.2 108.1 86.8
6750
72 192.4 17.6 149.4 126.5 103.6 80.8 - - 187.0 19.3 147.1 124.3 101.4 78.6 - -
67 177.9 17.3 175.3 156.2 133.4 110.5 87.7 - 172.7 18.9 171.7 154.2 131.4 108.5 85.7 -
62 165.6 17.1 165.6 165.6 162.1 139.2 116.3 93.5 163.2 18.7 163.2 163.2 160.1 137.5 114.4 91.6
57 162.6 17.0 162.6 162.6 159.9 137.0 114.1 91.3 158.1 18.7 158.1 158.1 155.3 132.9 109.6 86.8
7500
72 194.3 17.7 156.5 132.0 107.6 83.2 - - 189.2 19.3 154.2 129.9 105.5 81.1 - -
67 179.7 17.4 179.7 162.9 138.5 114.1 89.6 - 174.7 19.0 174.7 161.0 136.6 112.2 87.8 -
62 167.3 17.1 167.3 167.3 167.3 142.9 118.4 94.0 165.1 18.8 165.1 165.1 165.1 140.7 116.3 92.0
57 164.3 17.1 164.3 164.3 164.3 139.8 115.4 91.0 159.9 18.7 159.9 159.9 159.9 135.6 111.2 86.8
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YD / Two J07NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65