Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
58 Johnson Controls Unitary Products
115°F 125°F
6000
77 233.9 23.2 115.1 91.7 68.3 - - - 213.8 25.4 108.3 85.0 61.6 - - -
72 216.2 22.8 151.9 128.5 105.1 81.8 - - 199.1 25.0 145.6 122.3 99.0 75.6 - -
67 198.5 22.4 188.7 165.3 141.9 118.6 95.2 - 184.4 24.6 182.9 159.6 136.3 113.0 89.6 -
62 187.4 22.2 187.4 187.4 172.3 148.9 125.5 102.1 174.5 24.3 174.5 174.5 162.9 139.5 116.2 92.9
57 189.8 22.0 189.8 189.8 168.5 145.1 121.7 98.3 176.3 24.0 176.3 176.3 156.9 133.6 110.2 86.9
7000
77 241.4 23.4 135.1 100.9 74.4 - - - 221.7 25.6 132.6 94.5 67.7 - - -
72 223.2 23.0 167.6 141.0 114.5 87.9 - - 206.4 25.2 162.1 135.4 108.6 81.9 - -
67 204.9 22.6 200.0 181.1 154.6 128.0 101.5 - 191.2 24.8 191.2 176.3 149.5 122.8 96.1 -
62 193.5 22.3 193.5 193.5 187.6 161.1 134.5 108.0 180.9 24.5 180.9 180.9 178.8 152.7 125.3 98.6
57 195.9 22.1 195.9 195.9 183.4 156.9 130.4 103.8 182.7 24.1 182.7 182.7 172.3 146.5 118.8 92.1
8000
77 249.0 23.5 155.0 110.2 80.5 - - - 229.6 25.7 156.9 103.9 73.8 - - -
72 230.1 23.1 183.2 153.5 123.8 94.1 - - 213.8 25.3 178.6 148.4 118.3 88.2 - -
67 211.3 22.8 211.3 196.8 167.2 137.5 107.8 - 198.0 24.9 198.0 192.9 162.8 132.7 102.5 -
62 199.5 22.5 199.5 199.5 202.9 173.2 143.5 113.9 187.3 24.7 187.3 187.3 187.3 165.9 134.4 104.3
57 202.0 22.3 202.0 202.0 198.4 168.7 139.0 109.3 189.2 24.3 189.2 189.2 187.6 159.3 127.4 97.2
9000
72 237.2 23.2 198.2 165.7 133.2 100.7 - - 221.3 25.4 194.3 161.4 128.6 95.7 - -
67 217.8 22.8 217.8 210.6 179.8 147.3 114.9 - 205.0 25.0 205.0 205.0 176.8 143.9 111.1 -
62 205.7 22.5 205.7 205.7 207.4 174.9 142.4 109.9 193.9 24.7 193.9 193.9 193.9 165.4 131.9 99.0
57 208.3 22.3 208.3 208.3 206.4 174.0 141.5 109.0 195.9 24.4 195.9 195.9 195.1 163.2 129.4 96.5
10000
72 244.3 23.2 213.2 177.9 142.6 107.3 - - 228.9 25.4 210.0 174.4 138.8 103.2 - -
67 224.4 22.9 224.4 224.4 192.5 157.2 121.9 - 211.9 25.1 211.9 211.9 190.8 155.2 119.6 -
62 211.8 22.6 211.8 211.8 211.8 176.5 141.3 106.0 200.5 24.8 200.5 200.5 200.5 164.9 129.3 93.7
57 214.5 22.4 214.5 214.5 214.5 179.2 143.9 108.6 202.6 24.4 202.6 202.6 202.6 167.0 131.4 95.8
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20PC/J20NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65