Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 61
Heat Pump And Air Handler Heating Capacities
J07PC / J07NC
Air Over Evaporator Coil
Capacity
1
&
kW
Outdoor Temperature (°F @ 72% RH)
CFM DB (°F) -10 0 10 20 30 40 50 60
2250
55
MBH 34.0 39.6 46.2 53.9 62.9 73.5 86.0 100.6
KW 4.9 5.3 5.6 6.0 6.3 6.7 7.0 7.3
70
MBH 31.0 36.6 43.2 50.9 60.0 70.6 83.0 97.6
KW 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.2
80
MBH 28.7 34.3 40.9 48.6 57.7 68.3 80.7 95.3
KW 6.4 6.8 7.1 7.4 7.8 8.1 8.5 8.8
3000
55
MBH 35.3 40.9 47.5 55.2 64.3 74.9 87.3 101.9
KW 4.7 5.1 5.4 5.8 6.1 6.5 6.8 7.1
70
MBH 32.4 38.0 44.5 52.3 61.3 71.9 84.4 99.0
KW 5.6 5.9 6.3 6.6 6.9 7.3 7.6 8.0
80
MBH 30.1 35.7 42.3 50.0 59.0 69.6 82.1 96.7
KW 6.2 6.5 6.9 7.2 7.6 7.9 8.3 8.6
3750
55
MBH 36.6 42.2 48.8 56.5 65.6 76.2 88.6 103.2
KW 5.2 5.6 5.9 6.3 6.6 7.0 7.3 7.6
70
MBH 33.7 39.3 45.8 53.6 62.6 73.2 85.7 100.3
KW 6.1 6.4 6.8 7.1 7.4 7.8 8.1 8.5
80
MBH 31.4 37.0 43.6 51.3 60.3 70.9 83.4 98.0
KW 6.7 7.0 7.4 7.7 8.1 8.4 8.8 9.1
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated
motor efficiency.
J10PC / J10NC
Air Over Evaporator Coil
Capacity
1
&
kW
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated
motor efficiency.
Outdoor Temperature (°F @ 72% RH)
CFM DB (°F) -10 0 10 20 30 40 50 60
3000
55
MBH 29.1 36.4 45.3 56.0 69.0 84.7 103.8 126.8
KW 6.9 7.3 7.6 8.0 8.3 8.7 9.1 9.4
70
MBH 26.3 33.6 42.4 53.1 66.1 81.8 100.9 124.0
KW 8.2 8.6 8.9 9.3 9.7 10.0 10.4 10.7
80
MBH 24.2 31.5 40.4 51.1 64.1 79.8 98.8 121.9
KW 9.2 9.6 10.0 10.3 10.7 11.1 11.4 11.8
4000
55
MBH 37.4 44.7 53.5 64.3 77.2 93.0 112.0 135.1
KW 6.7 7.1 7.4 7.8 8.1 8.5 8.9 9.2
70
MBH 34.5 41.8 50.7 61.4 74.4 90.1 109.2 132.2
KW 8.0 8.4 8.7 9.1 9.5 9.8 10.2 10.6
80
MBH 32.5 39.8 48.6 59.3 72.3 88.0 107.1 130.2
KW 9.0 9.4 9.8 10.1 10.5 10.9 11.2 11.6
5000
55
MBH 44.1 51.4 60.3 71.0 84.0 99.7 118.7 141.8
KW 6.9 7.2 7.6 8.0 8.3 8.7 9.0 9.4
70
MBH 41.3 48.6 57.4 68.1 81.1 96.8 115.9 138.9
KW 8.2 8.6 8.9 9.3 9.6 10.0 10.4 10.7
80
MBH 39.2 46.5 55.3 66.1 79.0 94.8 113.8 136.9
KW 9.2 9.6 9.9 10.3 10.7 11.0 11.4 11.7