Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 75
Sound Performance
Outdoor Sound Power Levels (dB), 60 Hz
Size
(Tons)
Model
Sound
Rating
1
Octave Bands (Hz)
63 125 250 500 1000 2000 4000 8000
J07
(7.5)
J07PC 89 88 90 89 87 84 81 77 72
J07YC 89 88 89 89 87 84 81 78 73
J10
(10.0)
J10PC 89 88 90 89 87 84 81 77 72
J10YC 90 91 87 90 88 85 80 76 70
J10YD 90 92 89 91 88 85 80 77 71
J12
(12.5)
J12YC 91 96 88 90 89 86 82 77 71
J12YD 91 92 92 92 89 86 81 78 73
J15
(15.0)
J15PC 93 93 96 93 90 89 84 77 71
J15PD 93 93 96 93 90 89 84 77 71
J15YC 89 88 90 89 87 84 81 77 72
J15YD 89 88 90 89 87 84 81 77 72
J20
(20.0)
J20PC 93 93 96 93 90 89 84 77 71
J20PD 93 93 96 93 90 89 84 77 71
J20YC 93 93 96 93 90 89 84 77 71
J20YD 93 93 96 93 90 89 84 77 71
J25
(25.0)
J25YC 93 93 96 93 90 89 84 77 71
1
Rated in accordance with ARI 270 Standard.