Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet
Model
Compressors Outdoor Fan Motor Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
J07YC
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 5.0 22.6 30
575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 4.0 17.1 25
J10YC
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 10.0 56.8 70
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 5.0 28.5 35
575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 4.0 22.0 25
J10YD
208/230-3-60 2 17.3 27 123 208/230-1-60 3/4 2 3.0 10.0 55.0 70
460-3-60 2 9.6 15 70 460-1-60 3/4 2 1.6 5.0 29.8 35
575-3-60 2 7.7 12 53 575-1-60 3/4 2 1.4 4.0 24.0 30
J12YC
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 10.0 66.5 80
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 5.0 32.1 40
575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 4.0 24.0 30
J12YD
208/230-3-60 2 23.1 36 160 208/230-1-60 3/4 2 3.0 10.0 68.0 90
460-3-60 2 12.2 19 87 460-1-60 3/4 2 1.6 5.0 35.7 45
575-3-60 2 8.7 14 62 575-1-60 3/4 2 1.4 4.0 26.3 30
J15YC
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
J15YD
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
J20YC
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
J20YD
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
J25YC
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 10.0 130.3 175
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 5.0 53.3 70
575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 4.0 42.5 50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.