Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 27
115°F 125°F
3750
77 148.6 15.3 73.8 57.6 41.4 - - - 134.2 17.0 69.2 53.1 36.9 - - -
72 138.6 15.1 97.6 81.4 65.3 49.1 - - 128.0 16.7 93.8 77.6 61.5 45.3 - -
67 128.6 14.8 121.5 105.3 89.1 72.9 56.7 - 121.7 16.3 118.3 102.2 86.0 69.9 53.7 -
62 119.7 14.5 119.7 119.7 114.2 98.0 81.8 65.7 111.5 16.0 111.5 111.5 110.2 94.1 77.9 61.8
57 123.4 14.7 123.4 123.4 109.0 92.8 76.7 60.5 115.7 16.3 115.7 115.7 101.5 85.3 69.2 53.0
4375
77 155.4 15.4 88.5 64.6 45.9 - - - 142.1 17.0 86.4 60.4 41.5 - - -
72 145.0 15.1 109.7 91.0 72.3 53.6 - - 135.4 16.6 106.7 87.8 68.9 50.0 - -
67 134.5 14.8 130.9 117.4 98.7 80.0 61.2 - 128.7 16.3 127.0 115.2 96.4 77.5 58.6 -
62 125.3 14.5 125.3 125.3 126.5 107.8 89.0 70.3 118.0 16.0 118.0 118.0 118.0 105.0 85.7 66.8
57 129.1 14.7 129.1 129.1 120.7 102.0 83.3 64.6 122.4 16.3 122.4 122.4 113.8 95.2 76.0 57.1
5000
77 162.3 15.4 103.2 71.6 50.3 - - - 150.0 16.9 103.5 67.6 46.0 - - -
72 151.3 15.1 121.8 100.6 79.3 58.0 - - 142.8 16.6 119.6 98.0 76.3 54.7 - -
67 140.4 14.8 140.4 129.5 108.3 87.0 65.7 - 135.6 16.3 135.6 128.3 106.7 85.1 63.5 -
62 130.8 14.5 130.8 130.8 138.8 117.5 96.2 75.0 124.4 16.0 124.4 124.4 124.4 115.8 93.5 71.9
57 134.8 14.7 134.8 134.8 132.5 111.2 90.0 68.7 129.0 16.2 129.0 129.0 126.0 105.2 82.8 61.2
5625
72 154.3 15.2 133.5 110.3 87.0 63.8 - - 144.6 16.7 130.8 107.3 83.8 60.3 - -
67 143.2 14.9 143.2 137.8 118.8 95.5 72.3 - 137.4 16.4 137.4 134.1 117.1 93.6 70.1 -
62 133.4 14.6 133.4 133.4 137.4 114.1 90.8 67.6 126.0 16.1 126.0 126.0 126.0 109.0 85.1 61.6
57 137.4 14.8 137.4 137.4 136.3 113.0 89.8 66.5 130.7 16.3 130.7 130.7 129.2 106.1 82.2 58.7
6250
72 157.3 15.3 145.3 120.0 94.7 69.5 - - 146.4 16.8 142.0 116.6 91.2 65.8 - -
67 146.0 15.0 146.0 146.0 129.3 104.1 78.8 - 139.2 16.5 139.2 139.2 127.5 102.1 76.7 -
62 136.0 14.7 136.0 136.0 136.0 110.7 85.4 60.2 127.6 16.2 127.6 127.6 127.6 102.2 76.8 51.4
57 140.1 14.9 140.1 140.1 140.1 114.8 89.6 64.3 132.4 16.5 132.4 132.4 132.4 107.0 81.6 56.2
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J12YD/J15ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65