Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
56 Johnson Controls Unitary Products
115°F 125°F
4500
77 175.7 18.9 91.5 72.9 54.3 - - - 159.4 20.8 86.6 67.9 49.2 - - -
72 162.2 18.6 123.9 105.3 86.8 68.2 - - 147.1 20.5 119.1 100.5 81.8 63.1 - -
67 148.6 18.2 148.6 137.8 119.2 100.6 82.0 - 134.7 20.1 134.7 133.1 114.4 95.7 77.1 -
62 141.5 18.1 141.5 141.5 141.5 123.0 104.4 85.8 129.9 20.0 129.9 129.9 129.9 115.2 96.5 77.8
57 144.4 18.1 144.4 144.4 135.6 117.1 98.5 79.9 133.6 20.1 133.6 133.6 125.3 106.6 88.0 69.3
5250
77 177.4 18.9 109.8 77.2 56.0 - - - 160.8 20.9 109.2 72.0 50.7 - - -
72 163.7 18.6 131.8 110.6 89.4 68.2 - - 148.4 20.5 126.8 105.5 84.3 63.0 - -
67 150.0 18.3 150.0 144.0 122.8 101.6 80.4 - 135.9 20.1 135.9 135.9 117.8 96.5 75.3 -
62 142.9 18.1 142.9 142.9 146.6 125.4 104.2 82.9 131.0 20.0 131.0 131.0 131.0 118.0 96.4 75.2
57 145.8 18.1 145.8 145.8 139.8 118.5 97.3 76.1 134.8 20.1 134.8 134.8 129.1 108.2 86.5 65.2
6000
77 179.0 18.9 128.1 81.5 57.6 - - - 162.3 20.9 131.9 76.1 52.2 - - -
72 165.2 18.6 139.8 115.9 92.0 68.2 - - 149.7 20.5 134.5 110.6 86.7 62.8 - -
67 151.4 18.3 151.4 150.3 126.4 102.6 78.7 - 137.1 20.1 137.1 137.1 121.3 97.4 73.5 -
62 144.2 18.1 144.2 144.2 151.7 127.8 103.9 80.1 132.2 20.0 132.2 132.2 132.2 120.9 96.4 72.5
57 147.1 18.2 147.1 147.1 143.9 120.0 96.1 72.3 136.0 20.1 136.0 136.0 132.8 109.8 85.0 61.1
6750
72 167.3 18.7 151.0 124.5 97.9 71.4 - - 151.6 20.6 146.3 119.6 92.8 66.1 - -
67 153.3 18.3 153.3 152.8 134.6 108.0 81.5 - 138.9 20.2 138.9 138.9 129.8 103.0 76.3 -
62 146.0 18.1 146.0 146.0 149.8 123.2 96.7 70.2 133.9 20.0 133.9 133.9 133.9 113.5 86.4 59.6
57 149.0 18.2 149.0 149.0 147.4 120.9 94.3 67.8 137.7 20.1 137.7 137.7 136.1 109.9 82.6 55.9
7500
72 169.4 18.7 162.2 133.0 103.9 74.7 - - 153.5 20.6 153.5 128.6 99.0 69.4 - -
67 155.3 18.4 155.3 155.3 142.7 113.5 84.3 - 140.7 20.3 140.7 140.7 138.3 108.7 79.1 -
62 147.9 18.2 147.9 147.9 147.9 118.7 89.5 60.3 135.6 20.1 135.6 135.6 135.6 106.0 76.4 46.8
57 150.9 18.3 150.9 150.9 150.9 121.7 92.5 63.3 139.5 20.2 139.5 139.5 139.5 109.9 80.3 50.6
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15PD/J15ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65