Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 39
115°F 125°F
4500
77 200.6 18.3 104.5 85.3 66.0 - - - 195.5 20.2 102.5 83.2 64.0 - - -
72 186.0 17.8 129.7 110.5 91.2 72.0 - - 181.6 19.6 127.9 108.6 89.4 70.1 - -
67 171.4 17.4 154.9 135.7 116.4 97.2 77.9 - 167.7 19.1 153.2 134.0 114.7 95.5 76.3 -
62 153.0 16.9 153.0 153.0 136.1 116.8 97.6 78.3 148.7 18.5 148.7 148.7 133.0 113.8 94.5 75.3
57 156.4 16.9 156.4 156.4 139.2 120.0 100.7 81.5 153.5 18.5 153.5 153.5 136.4 117.1 97.9 78.7
5250
77 207.4 18.4 117.0 93.6 71.5 - - - 202.4 20.4 115.6 91.6 69.5 - - -
72 192.3 18.0 143.0 120.9 98.9 76.8 - - 188.1 19.8 141.2 119.1 97.0 75.0 - -
67 177.2 17.5 169.0 148.3 126.2 104.1 82.0 - 173.7 19.2 166.7 146.6 124.6 102.5 80.4 -
62 158.2 17.0 158.2 158.2 147.5 125.4 103.3 81.2 154.0 18.7 154.0 154.0 144.4 122.5 100.2 78.2
57 161.8 17.0 161.8 161.8 150.9 128.8 106.7 84.6 158.9 18.7 158.9 158.9 148.1 126.3 103.9 81.9
6000
77 214.3 18.6 129.6 102.0 77.1 - - - 209.4 20.5 128.8 99.9 75.0 - - -
72 198.7 18.1 156.3 131.4 106.5 81.6 - - 194.5 20.0 154.5 129.6 104.7 79.8 - -
67 183.1 17.6 183.1 160.9 135.9 111.0 86.1 - 179.7 19.4 179.7 159.3 134.4 109.5 84.6 -
62 163.5 17.1 163.5 163.5 158.8 133.9 109.0 84.1 159.3 18.8 159.3 159.3 155.8 131.2 106.0 81.1
57 167.1 17.1 167.1 167.1 162.6 137.6 112.7 87.8 164.4 18.8 164.4 164.4 159.8 135.5 110.0 85.1
6750
72 200.5 18.1 166.3 139.0 111.8 84.5 - - 196.0 19.9 164.4 137.1 109.8 82.6 - -
67 184.7 17.6 184.7 169.9 142.6 115.4 88.1 - 181.0 19.4 181.0 168.3 141.0 113.8 86.5 -
62 164.9 17.1 164.9 164.9 162.6 135.4 108.1 80.8 160.4 18.8 160.4 160.4 158.7 131.6 104.2 76.9
57 168.6 17.1 168.6 168.6 166.3 139.1 111.8 84.6 165.6 18.8 165.6 165.6 163.3 136.4 108.8 81.5
7500
72 202.3 18.1 176.2 146.6 117.0 87.4 - - 197.4 19.9 174.2 144.6 115.0 85.4 - -
67 186.4 17.6 186.4 178.9 149.3 119.7 90.1 - 182.3 19.3 182.3 177.2 147.6 118.0 88.4 -
62 166.4 17.1 166.4 166.4 166.4 136.8 107.2 77.6 161.6 18.7 161.6 161.6 161.6 132.0 102.4 72.8
57 170.1 17.1 170.1 170.1 170.1 140.5 110.9 81.3 166.8 18.7 166.8 166.8 166.8 137.2 107.6 78.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YD/J20ND (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65