Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 35
115°F 125°F
6000
77 226.4 15.9 115.7 92.1 68.4 - - - 223.0 16.7 114.4 90.8 67.1 - - -
72 210.6 15.6 150.7 127.1 103.5 79.8 - - 207.7 16.4 149.7 126.1 102.5 78.8 - -
67 194.9 15.3 185.7 162.1 138.5 114.9 91.2 - 192.4 16.1 185.0 161.4 137.8 114.1 90.5 -
62 185.6 15.0 185.6 183.5 159.8 136.2 112.6 89.0 186.1 15.8 186.1 183.2 159.5 135.9 112.3 88.7
57 185.6 15.0 185.6 183.5 159.9 136.3 112.6 89.0 183.8 15.8 183.8 181.1 157.5 133.9 110.3 86.7
7000
77 228.3 17.1 135.1 99.6 72.9 - - - 223.2 18.5 135.2 97.9 71.3 - - -
72 212.4 16.8 163.5 136.9 110.3 83.6 - - 207.9 18.2 162.0 135.4 108.8 82.1 - -
67 196.5 16.5 191.9 174.2 147.6 121.0 94.3 - 192.6 17.9 188.9 172.9 146.3 119.6 93.0 -
62 187.1 16.2 187.1 186.1 170.4 143.7 117.1 90.5 186.3 17.5 186.3 184.8 169.4 142.6 116.1 89.5
57 187.1 16.2 187.1 186.1 170.4 143.8 117.1 90.5 184.0 17.5 184.0 182.6 167.2 141.0 114.0 87.3
8000
77 230.2 18.3 154.5 107.1 77.4 - - - 223.4 20.2 156.0 105.1 75.4 - - -
72 214.2 18.0 176.3 146.7 117.1 87.4 - - 208.1 19.9 174.4 144.7 115.1 85.5 - -
67 198.2 17.7 198.2 186.3 156.7 127.1 97.4 - 192.7 19.6 192.7 184.4 154.8 125.1 95.5 -
62 188.7 17.3 188.7 188.7 180.9 151.2 121.6 92.0 186.5 19.2 186.5 186.5 179.3 149.2 120.0 90.3
57 188.7 17.3 188.7 188.7 180.9 151.3 121.6 92.0 184.2 19.1 184.2 184.2 176.9 148.2 117.7 88.0
9000
72 216.2 17.9 185.9 154.0 122.0 90.1 - - 209.6 19.8 183.6 151.7 119.8 87.9 - -
67 200.1 17.6 200.1 194.1 163.4 131.4 99.5 - 194.2 19.5 194.2 191.3 161.1 129.2 97.3 -
62 190.5 17.3 190.5 190.5 186.6 154.7 122.7 90.8 187.9 19.1 187.9 187.9 184.3 152.2 120.5 88.6
57 190.5 17.3 190.5 190.5 186.6 154.7 122.8 90.8 185.5 19.0 185.5 185.5 181.9 150.5 118.1 86.2
10000
72 218.3 17.9 195.5 161.3 127.0 92.8 - - 211.1 19.7 192.8 158.6 124.5 90.3 - -
67 202.0 17.6 202.0 202.0 170.0 135.8 101.6 - 195.6 19.4 195.6 195.6 167.4 133.3 99.1 -
62 192.3 17.2 192.3 192.3 192.3 158.1 123.8 89.6 189.3 19.0 189.3 189.3 189.3 155.2 121.0 86.9
57 192.3 17.2 192.3 192.3 192.3 158.1 123.9 89.6 186.9 18.9 186.9 186.9 186.9 152.8 118.6 84.5
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YD / Two J10NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65