Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 29
115°F 125°F
4500
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - -
72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - -
67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 -
62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4
57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8
5250
77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - -
72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - -
67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 -
62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1
57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7
6000
77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - -
72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - -
67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 -
62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8
57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6
6750
72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - -
67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 -
62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4
57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2
7500
72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - -
67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 -
62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9
57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YC/J15NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65