Bryant 548J Heat Pump User Manual


 
65
are restored and phase sequence is correct. If no 24-v
control power is available to the PMR, the red LED wil l
be off.
RTU-- MP Sequence of Operation
The RTU--MP will control the compressor, economizer
and heating outputs based on its own space temperature
input and setpoints. An opt ional CO
2
IAQ sensor mounted
in the space can influence the economizer minimum
position. The RTU--MP has its own hardware clock that is
set automatically when the software is installed on the
board. The RTU--MP’s default i s to cont rol to occupied
setpoints all the time, until a type of occupancy control is
set. Occupancy types are described in the scheduling
section. The following secti ons describe the operation for
the functions of the RTU--MP. All point objects that are
referre d to in this sequence wil l be in reference to the
objec ts as viewed in BACview
6
Handheld.
Scheduling
Scheduling is used to start heating or cooling (become
occupied) based upon a day of week and a time period and
control to the occupied heating or cooling setpoints.
Scheduling functions are loca ted under occupancy
determination and the schedule menu accessed by the
Menu softkey (see Form 48--50H--T--2T, Appendix -- for
menu structure). Your local time and date should be set
for these functions to operate properly. Five scheduling
functions are available by changing the Occupancy Source
to one of the following selections:
Always Occupied (Default Occupancy)
The unit will run continuously. RTU--MP ships from t he
factory with this setting.
Local Schedule
The unit will operate according to the schedule configured
and stored in the unit. The local schedule is made up of
three hierarchy levels that consist of two Override
schedule s, twelve Holiday and four Daily schedules, and
are only accessible by the BACview screen (handheld or
virtual).
The Daily schedule is the lowest schedule in the hierarchy
and is overridden by both the Holiday and Override
schedule. It consists of a start time, a stop time (both in 24
hour mode) and the seven days of the wee k, starting with
Monday and ending in Sunday. To select a daily schedule
scroll to the Schedules menu off of the Menu selection.
Enter the User password and change the Occupa ncy
Source to Local Sche dule. Scroll down and over to the
Daily menu and press enter. Choose one of the four Daily
schedule s by pre ssing the Next softkey and change the
Use? point from NO to YES by se lecting the point and
pressing the INCR or DECR softkey. Press the OK softkey
and scroll to the start and stop times. Edit these times
following the same steps as the Use? point. Finally scroll
down t o the Days: sect ion and highlight the da ys required
for the Dail y schedule by INCR or DECR softkeys and
press OK softkey.
The Holiday schedule is c reated to override the Daily
schedule and identify a specifi c day and month of the year
to start and stop the unit and change control to the
unoccupi ed heating and c ooling setpoints. Follow the
same steps to turn on one of the twelve Holiday sche dules
and start and stop times. Next, select one out of the twelve
months and one out of the thirty--one days of that month.
The RTU--MP will now ignore the Daily schedule for the
specific day and time you selected and follow the Holiday
Schedule for this period.
The Override schedules primary purpose is to provide a
temporary change in the occupied heat ing and cooling
setpoints and force the unit to control to the unoccupied
heat ing and cooli ng setpoint s. This would occur on a set
day in a particular month and last during the start and stop
time configured. The Override schedule is enabled by
following the same steps to create the Holiday schedule.
NOTE: Push button override is only a vailable when
running a local or BACnet Schedule.
BACnet Schedule
For use with a Building Automation System that supports
native BACnet scheduling is scheduling the unit. With the
Occupancy Source set to BACnet schedule the BAS will
control the unit through network communication and it’s
own scheduling function.
BAS On/Off
The Building Automa tion System is scheduling the unit
via an On/Off command to the BAS ON/OFF software
point. The Building Automation System can be speaking
BACnet, Modbus, or N2 and is writing to t he BAS On/Off
point i n the open protocol point map.
NOTE: If the BAS supports NATI VE BACnet
scheduling, then set the Occupancy Source to BACnet
schedule . If the BAS is BACnet but does NOT support
NATIVE BACnet scheduling, then set the Occupancy
Source to BAS On/Off.
DI On/Off
A hard--wired input on the RTU--MP will command the
unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be
hard--wired to command the unit to start/stop.
NOTE: Scheduling can either be controlled via the unit
or the BAS, but NOT both.
Indoor
Fan
The indoor fan will be turned on whenever any one of the
following condit ions is true:
S It is in the occupied mode. This will be determined by its
own internal occupancy schedule.
S Whenever there is a demand for cooling or heating in the
unoccupi ed mode.
S Whenever the remote occupancy switch is closed during
DI On/Off schedule type or i f occupancy is forced
occupi ed by the BAS during BAS On/Off schedule type.
When transitioning from unoccupi ed to occupied, there
will be a configured time delay of 5 to 600 seconds before
starting the fan. The fan will continue to run as long as
compressors, heating stages, or the dehumidification
relays are on when transit ioning from occupied to
unoccupi ed with the exception of Shutdown mode. If Fire
Shutdown, safety chain, SAT alarm or SPT alarm are
active; the fan will be shutdown immediately regardless of
the occupancy state or demand.
The RTU--MP has an optional Supply Fan Status input to
provide proof of airflow. If this is enabled, the point will
548J