Bryant 548J Heat Pump User Manual


 
44
Alarms
Alarms can be checked through the network and/or the
local access. All the alarms are listed in Table 17 with
name , objec t name, action t ake n by c ontrol, re set method,
and probable cause. There are help screens for each alarm
on the local access display and listed in Form
48--50H--T--2T, Appendix A: He lp Scree ns. Some alarms
are explained in detail below.
Safety Chain
Alarm
This alarm occurs immediately if the supply--fan internal
overload trips or if an electric--heat limit switch trips. The
Unit Status will be Shutdown and the System Mode will
be Disable. When this happens CTB (R te rminal) will not
have 24 VAC, but the RTU--MP board will still be
powered. All unit operations stop immediately and will
not restart until the alarm automatically clears. There are
no confi gurations for this alarm; it is all based on internal
wiring. This alarm will never occur if Fire Shutdown
Alarm is active.
Fire Shutdown
Alarm
This alarm occurs immediately when the smoke detector
senses smoke. The Unit Status will be Shutdown and the
System Mode will be Disable. All unit operations stop
immediately and will not restart until the alarm
automatically clears. If there is not a smoke detector
installed or the smoke detector did not trip, check input
configurations.
Space Tem p Sensor Failur
e
This alarm occurs if the space sensor wired to the
RTU--MP is disconnected or shorted for more then 10
seconds. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
SAT Sensor
Alarm
This alarm occurs immediately when t he supply air
temperature sensor wired to the RTU--MP is disconnected
or shorted. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
Switch Configuration
Alarm
This occurs if more than one binary input (inputs 3, 5, 8,
and 9) is configured for the same function. When this
happens the two inputs (or more) configured wrong will
be disabled a s an inputs. This a larm will autom atically be
cleared when configuration is corrected.
An exa mple of this would be: Input 3 = Compressor
Safety, input 5 = Fan Status, input 8 = Fan Status, and
input 9 = Humidistat; the alarm would be active, unit
would run, com pressor safety and humidistat would
function normally, and Fan Status (inputs 5 & 8) will be
interpreted as “No Function.”
Misconfigured Analog
Input
This occurs if more than one analog input (inputs 1 & 2)
is configured for the same sensor. When this happens the
two inputs wil l be disabled as inputs. This alarm will
automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input
2 = IAQ Sensor; the alarm would be active , unit would
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted
as “No Function.”
Third Party
Networking
Third party communication and networking
troubleshooting should be done by or with assistance from
the front end 3rd party technician. A Module Status
Report (Modstat) (see Fig. 65) can be run from the
BACview
6
, see Table 18 to perform. This lists information
about the board status and networking state. For basic
troubleshooting, see Table 19. Refer to the RTU--MP 3rd
Party Inte gration Guide for additi onal information.
BACnet MS/TP
1. Verify that the BAS and controller are both set to
speak the BACnet MS/TP protocol. The protocol of
the control ler is set via SW3 (switches 3, 4, 5, and 6).
The protocol can also be verified by getting a Modstat
of the controller through the BACview. Hit the “FN”
key and the “.” key at the same time to pull up a
Modstat. Scroll to the bottom of the page and there is
a section entitled “Network Communications.” The
active protocol and baud ra te will be shown in this
section.
2. Verify that the BAS and controller are set for the
same baud rate. The ba ud rate of the controller is set
via SW3 (switches 1 and 2). The baud rate can also
be verified via the BACview by obtaining a Modsta t.
(See Fig. 65.)
3. Verify that the BAS is configured to speak 2 -- wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on t heir end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the c ontroller has a unique MAC addre ss
on the MS/TP bus. The controller’s MS/TP MAC
address is set by its rotary address switches.
6. Verify proper wiring between the BAS and the
controller.
7. Verify that the BAS is reading or writing to the proper
BACnet objects in the controller. Download the latest
points li st for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper MS/TP MAC address of our controller.
9. Pre sent the BAS company with a copy of our
controller’s BACnet PICS so that they know which
BACnet commands are supported. See below.
10. In certain situations, it may be necessary to tweak the
MS/TP Protocol timing settings through the
BACview
6
. There are two settings that may be
tweaked: