Bacharach 24-9448 Carbon Monoxide Alarm User Manual


 
Instruction 24-9448 4-31
Operation
Figure 4-3. Printer Alignment & Sample Printout
BACHARACH, INC.
PCA 2
SN: xxxxxx
=====================
TIME 01:00:00 PM
DATE 10/06/06
FUEL
NATURAL GAS
O2 4.0 %
CO 12 ppm
EFF 82.6 %
CO2 9.5 %
T-STACK 374 °F
T-AIR 68.0 °F
EA 21 %
NO 18 ppm
NO Temp 70.5 °F
NO2 6 ppm
NOX 24 ppm
SO2 ∗∗∗ ppm
CO(3) 13 ppm
NO(3) 19 ppm
NO2(3) 6 ppm
NOX(3) 25 ppm
SO2(3) ∗∗∗ ppm
PRESSURE –0.25 inwc
COMMENTS:
PRINT MENU SAVE
3 to 18 in.
(7.62 to 45.72 cm)
NOTES:
Three stars (∗∗∗) appear in the data
eld of sensors that are not calibrated
or defective, and in the data elds of
that sensor’s related calculated values.
Three hyphens or dashes (- - -) indicate
that the calculated data cannot be
displayed because the measured data
necessary to make the calculation is
out of range (i.e., oxygen level above
16%).
Three (XXX) indicate sensor over-
range.
Optional
pressure printout
as selected per
Section 3.12.