Trane RAUC-C50 Air Conditioner User Manual


 
22 SS-SVX09A-EN
Installation
Table 1. Typical Unit Weights & Point Loading Data
Unit
Size
Operating
Weight
Unit Weight on Isolator @ Mounting Location
Location 123456
AL CU AL CU AL CU AL CU AL CU AL CU AL CU
C20 1522 1720 509 559 398 439 345 404 270 317
C25 1640 1842 555 602 421 467 378 436 286 338
C30 1824 2115 580 640 635 708 291 364 318 403
C40 2769 3102 480 523 457 501 473 528 450 506 466 533 443 511
C50 3148 3540 586 643 562 620 536 601 514 579 485 559 465 538
C60 3480 4050 640 722 618 703 590 684 570 666 540 646 522 629
Note: Mounting locations correlate with those shown in point loading illustration
Table 2. Typical EVP Chiller Weights & General Data
Chiller
Size
Shipping
Weight
2
Operating
Weight
Number of
Ref. Ckts.
Water Volume in
Gallons
3
Refrigerant Charge
in Lbs.
4
20 Ton 80 100 1 2.0 2.5
25 Ton 92 116 1 2.4 3.0
30 Ton 105 133 1 2.9 3.7
40 Ton 152 186 2 3.7 4.7
50 Ton 170 211 2 4.3 5.5
60 Ton 242 309 2 7.0 8.9
Notes:
2 - Shipping and Operating weights are approximate
3 - Includes volume of Water Piping Kit.
4 - Refrigerant charge is approximate for chiller evaporator only
Unit Size
Shipping
weight (Max.
Lbs)
Location of Center of Gravity
XZ
In mm In mm
C20 1724 38-1/16 968 26-3/8 671
C25 1843 38-1/16 968 26-3/16 666
C30 2107 34-1/16 865 31-1/2 800
C40 3088 44-3/16 1122 43-1/16 1095
C50 3532 54-11/16 1389 43-3/16 1097
C60 4024 55-3/16 1402 43-3/8 1102