63
Wiring Section 3-2
Terminal Screws and
Crimp Terminals
The terminals on the Power Supply Unit use M4 self-raising terminal screws.
Note (1) Use crimp terminals for wiring.
(2) Do not connect bare stranded wires directly to terminals.
(3) Tighten the terminal block screws to a torque of 1.2 N·m.
(4) Use M4 crimp terminals for AC power supplies.
Crimp Terminals for Ground Wire
LG
GR
Other equipmentFQM1
FQM1
FQM1
GR
LG
GR
Other equipment
GR
LG
GR
Other equipment
GR
Ground to
100 Ω or less.
Ground to
100 Ω or less.
Ground to
100 Ω or less.
Ground to
100 Ω or less.
7 mm max.
7 mm max.