Omron FQM1-MMP21 Home Security System User Manual


 
186
Pulse Outputs Section 7-6
Use PRV(881) to read the pulse output PV of the specified port.
Pulse Outputs without Acceleration/Deceleration (PULS(886): Electronic Cam
Control)
This procedure shows how to use the PULS(886) instruction’s electronic cam
control function to generate a single-phase pulse output without acceleration
or deceleration. The number of output pulses can be changed during position-
ing.
Procedure
1,2,3... 1. Determine pulse output port.
Select pulse output 1 or 2.
2. Wire the output.
Output: CW and CCW
Output power supply: 5 V DC
3. Make the necessary System Setup settings (Pulse Output Tab Page
Op-
eration Mode).
Set the pulse output operation mode (in the Pulse Output Tab Page
Operation Mode) to absolute linear pulse output (electronic cam control)
or absolute circular pulse output (electronic cam control).
Set the clock speed for pulse outputs 1 and 2.
4. Create the necessary ladder programming.
Use PULS(886) to set the absolute position, output frequency, and pulse
output (automatic determination of pulse output direction) for the specified
port.
Use INI(880) to stop pulse output from the specified port.
Use PRV(881) to read the pulse output PV of the specified port.
Electronic Cam Control
Functions
The electronic cam control supports the following functions.
The pulse output direction is determined automatically by comparing the
present position (pulse output PV) and target position.
The PULS(886) instruction can be executed during pulse output to
change the absolute position setting and pulse frequency.
Applications of Electronic Cam Operation:
PULS
INI
ACC
PRV
A621 A620
A623 A622
A624
A625
CW
CCW
CW
CCW
Pulse output
port 1
Pulse output
port 2
Single-phase
pulse output
(fixed duty ratio)
Start
output
Ladder program Ladder program
Set the number
of output pulses.
Stop pulse output.
Target frequency: 0 Hz to 1 MHz
Start pulse output.
Pulse output
mode
System Setup
Mode settings for
ports 1 and 2
Port 1
Port 2
Port 1
Port 2
Refresh status (once each cycle
just after instruction execution)
Pulse output status
Pulse output PV
Refresh PV (once each cycle) Refresh PV (immediate refresh)
SET PULSE
MODE CONTROL
HIGH-SPEED
COUNTER
PV READ
ACCELERTION
CONTROL
Mode settings (CW/CCW, accel-
eration/deceleration, independ-
ent/continuous)
Acceleration/deceleration rate
(common) (1 or 2 ms cycle,
1 Hz to 9,999 Hz)