Connecting the CX-Programmer Section 8-2
8-2 Connecting the CX-Programmer
8-2-1 System Configuration
Connecting a Personal Computer Running Support Software
Connecting to the Peripheral Port
Connecting to the RS-232C Port
Programming Software
Note When the CX-Programmer is used with an FQM1, the CX-Programmer ver-
sion must be Version 5.0 or higher and the FQM1 Patch Software must be
installed.
Computer
Windows
OS
Computer connector
D-Sub, 9-pin
D-Sub, 9-pin
D-Sub, 9-pin
Length
0.1 m
2.0 m
6.0 m
Peripheral port
RS-232C
Peripheral port
CS1W-CN118
Cable
CS1W-CN118 (See note 1.)
CS1W-CN226
CS1W-CN626
CM MM
MMCM
Computer
(RS-232C, 9-pin)
Connecting Cables for Peripheral Port
1. The CS1W-CN118 Cable is used with an RS-232C cable to connect to the peripheral port on the
Coordinator Module as shown below. Peripheral bus communications cannot be used if the CS1W-CN118
Cable is combined with an RS-232C Cable that has a model number ending in -V. In this case, Host Link
(SYSMAC WAY) communications must be used.
Note
XW2Z-@@@S-@@
(See note 2.)
RS-232C Cable
2. Host Link (SYSMAC WAY) communications cannot be used. Use peripheral bus communications.
CM
MM
Note
Computer
(RS-232C, 9-pin)
RS-232C Cable
XW2Z-200S-CV or XW2Z-200S-V: 2 m
XW2Z-500S-CV or XW2Z-500S-V: 5 m
The XW2Z-200S-CV and XW2Z-500S-CV use static-resistant
connectors and can be connected through peripheral bus or Host
Link communications. The XW2Z-200S-V and XW2Z-500S-V,
however, can only be connected through Host Link, not through
peripheral bus.
RS-232C port
OS Name
Microsoft Windows CX-Programmer Version 5.0 or higher only
(See note.)
CD-ROM