Section 3: Configuration
January 2013
Configuration
3.2.8 Reference K-factor
The reference K-factor is a factory calibration number relating the flow through the meter to the
shedding frequency measured by the electronics. Every 8600 meter manufactured by Emerson
is run through a water calibration to determine this value.
3.2.9 Flange type
Flange Type enables you to specify the type of flange on the flowmeter for later reference. This
variable is preset at the factory but can be changed if necessary.
ANSI 150
ANSI 300
PN16
PN40
Spcl
3.2.10 Mating pipe ID (Inside Diameter)
The Pipe ID (Inside Diameter) of the pipe adjacent to the flowmeter can cause entrance effects
that may alter flowmeter readings. You must specify the exact inside diameter of the pipe to
correct for these effects. Enter the appropriate value for this variable.
Pipe ID values for schedule 10, 40, and 80 piping are given in Tab le 3-1 . If the piping in your
application is not one of these, you may need to contact the manufacturer for exact Pipe ID.
f
3.2.11 Variable mapping
Allows the user to select which Variables the 8600D will output.
Field Comm. 1, 3, 3
Field Comm. 1, 3, 4
Field Comm. 1, 3, 5
Table 3-1. Pipe IDs for Schedule 10, 40, and 80 Piping
Pipe Size
Inches (mm)
Schedule 10
Inches (mm)
Schedule 40
Inches (mm)
Schedule 80
Inches (mm)
1 (25) 1.097 (27.86) 1.049 (26.64) 0.957 (24.31)
1½ (40) 1.682 (42.72) 1.610 (40.89) 1.500 (38.10)
2 (50) 2.157 (54.79) 2.067 (52.50) 1.939 (49.25)
3 (80) 3.260 (82.80) 3.068 (77.93) 2.900 (73.66)
4 (100) 4.260 (108.2) 4.026 (102.3) 3.826 (97.18)
6 (150) 6.357 (161.5) 6.065 (154.1) 5.716 (145.2)
8 (200) 8.329 (211.6) 7.981 (202.7) 7.625 (193.7)