Appendix C: Electronics verification
January 2013
Electronics verification
Appendix C Electronics verification
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 119
Electronics verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 120
Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 125
Electronics verification of the Model 8600D can be done by either utilizing the internal signal
simulation capability or by applying an external signal source to the “TEST FREQ IN” and
“GROUND” pins.
C.1 Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety
of the personnel performing the operations. Please
refer to the following safety messages before performing any operation in this section.
Explosions could result in death or serious injury:
Do not remove the transmitter cover in explosive atmospheres when the circuit is
alive.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Both transmitter covers must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury:
Make sure only qualified personnel perform the installation.
Remove power before removing the electronics housing.