York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
Johnson Controls Unitary Products 81
115°F 125°F
1875
77 87.0 8.8 31.8 27.6 20.5 - - - 80.5 9.7 27.4 25.2 18.3 - - -
72 79.6 8.7 47.8 40.7 33.6 26.5 - - 73.1 9.6 45.1 38.1 31.2 24.2 - -
67 72.2 8.7 63.8 53.7 46.6 39.5 32.4 - 65.8 9.6 62.5 51.1 44.1 37.1 30.1 -
62 66.5 8.6 66.5 66.5 54.1 47.0 39.9 32.8 60.5 9.5 60.5 60.5 49.8 42.8 35.8 28.9
2250
77 89.0 8.9 39.5 31.1 22.7 - - - 82.0 9.7 36.6 28.4 20.2 - - -
72 81.5 8.8 53.9 45.5 37.1 28.7 - - 74.5 9.7 50.9 42.6 34.4 26.2 - -
67 74.0 8.7 68.4 60.0 51.6 43.2 34.8 - 67.0 9.6 65.1 56.9 48.7 40.4 32.2 -
62 68.1 8.6 68.1 68.1 59.8 51.4 43.0 34.6 61.6 9.5 61.6 61.6 55.0 46.7 38.5 30.3
57 70.0 8.7 70.0 68.4 60.0 51.6 43.2 34.8 64.6 9.6 64.6 63.0 54.8 46.6 38.3 30.1
2625
77 91.1 8.9 47.2 34.5 24.8 - - - 83.6 9.8 45.8 31.5 22.0 - - -
72 83.4 8.8 60.0 50.3 40.6 31.0 - - 76.0 9.7 56.6 47.1 37.6 28.2 - -
67 75.7 8.8 72.9 66.2 56.5 46.8 37.1 - 68.3 9.6 67.8 62.7 53.2 43.8 34.3 -
62 69.7 8.7 69.7 69.7 65.5 55.9 46.2 36.5 62.8 9.6 62.8 62.8 60.1 50.7 41.2 31.7
57 71.6 8.7 71.6 70.8 65.8 56.1 46.4 36.7 65.8 9.6 65.8 65.0 60.0 50.5 41.0 31.5
3000
77 93.2 8.9 54.9 38.0 27.0 - - - 85.2 9.8 55.1 34.7 23.9 - - -
72 85.3 8.9 66.1 55.2 44.2 33.2 - - 77.4 9.7 62.3 51.6 40.9 30.2 - -
67 77.4 8.8 77.4 72.4 61.4 50.4 39.4 - 69.6 9.7 69.6 68.6 57.8 47.1 36.4 -
62 71.2 8.7 71.2 71.2 71.2 60.3 49.3 38.3 63.9 9.6 63.9 63.9 63.9 54.6 43.9 33.1
57 73.2 8.8 73.2 73.2 71.5 60.5 49.5 38.6 67.1 9.6 67.1 67.1 65.1 54.4 43.7 32.9
3375
72 86.6 8.9 70.2 58.6 47.0 35.3 - - 79.0 9.7 67.1 55.5 43.9 32.4 - -
67 78.6 8.8 78.6 76.1 65.2 53.6 42.0 - 71.1 9.7 71.1 71.1 62.1 50.5 39.0 -
62 72.3 8.7 72.3 72.3 72.3 60.7 49.1 37.5 65.3 9.6 65.3 65.3 65.3 54.4 42.9 31.3
57 74.4 8.8 74.4 74.4 73.5 61.9 50.2 38.6 68.5 9.6 68.5 68.5 67.5 55.9 44.4 32.8
3750
72 87.9 8.8 74.3 62.0 49.7 37.5 - - 80.7 9.7 71.8 59.4 47.0 34.6 - -
67 79.8 8.8 79.8 79.8 69.1 56.8 44.6 - 72.6 9.6 72.6 72.6 66.4 54.0 41.6 -
62 73.4 8.7 73.4 73.4 73.4 61.2 48.9 36.6 66.7 9.6 66.7 66.7 66.7 54.3 41.9 29.5
57 75.5 8.7 75.5 75.5 75.5 63.2 50.9 38.7 69.9 9.6 69.9 69.9 69.9 57.5 45.1 32.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR090 (7.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65