York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
102 Johnson Controls Unitary Products
Additional Static Resistance - ZJ078-150
Size
(Tons)
Model CFM Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
,
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4” Filter
2
Electric Heat kW
2
9 18243654
078 (6.5)
090 (7.5)
102 (8.5)
120 (10)
150 (12.5)
ZJ
1900 0.06 0.02 0.12 0.05 0.06 0.07 0.08 0.10
2100 0.07 0.02 0.13 0.06 0.07 0.08 0.09 0.11
2300 0.08 0.02 0.14 0.07 0.08 0.09 0.10 0.13
2500 0.09 0.02 0.16 0.08 0.09 0.10 0.11 0.14
2700 0.11 0.03 0.17 0.09 0.10 0.12 0.13 0.16
2900 0.12 0.03 0.19 0.10 0.11 0.13 0.14 0.18
3100 0.14 0.03 0.20 0.12 0.13 0.15 0.16 0.20
3300 0.16 0.03 0.22 0.13 0.14 0.17 0.18 0.22
3500 0.18 0.04 0.26 0.15 0.16 0.19 0.20 0.24
3700 0.20 0.04 0.27 0.17 0.18 0.21 0.22 0.26
3900 0.23 0.04 0.29 0.19 0.20 0.23 0.24 0.28
4100 0.25 0.04 0.32 0.21 0.22 0.25 0.26 0.31
4300 0.28 0.05 0.35 0.23 0.24 0.28 0.29 0.34
4500 0.30 0.05 0.38 0.25 0.26 0.30 0.31 0.37
4700 0.33 0.05 0.41 0.28 0.29 0.33 0.34 0.40
4900 0.36 0.05 0.44 0.30 0.31 0.35 0.37 0.43
5100 0.39 0.06 0.47 0.33 0.34 0.38 0.40 0.46
5300 0.42 0.06 0.51 0.35 0.37 0.41 0.43 0.49
5500 0.45 0.06 0.55 0.38 0.40 0.44 0.46 0.53
5700 0.48 0.06 0.58 0.41 0.43 0.47 0.49 0.56
5900 0.52 0.07 0.62 0.44 0.46 0.50 0.53 0.59
6100 0.56 0.07 0.67 0.47 0.49 0.53 0.56 0.62
6300 0.60 0.07 0.71 0.50 0.53 0.56 0.59 0.65