York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
Johnson Controls Unitary Products 79
75°F 85°F
1625
72 34.3 5.7 ----- 32.4 5.6 -----
67 34.2 5.4 1.3 1.2 1.1 1.0 - 32.2 5.6 0.3 0.4 0.5 0.6 -
62 30.6 5.0 4.3 4.2 4.1 4.0 3.9 28.2 4.8 2.1 2.2 2.2 2.3 2.4
1950
72 35.1 5.7 ----- 33.5 5.8 -----
67 35.0 5.4 4.0 3.5 3.0 2.6 - 33.3 5.7 3.0 2.7 2.3 1.9 -
62 31.3 5.0 12.4 12.0 11.5 11.0 10.6 29.1 4.9 11.0 10.6 10.3 9.9 9.5
57 31.2 5.0 14.6 14.2 13.7 13.3 12.8 29.4 4.9 12.2 11.9 11.5 11.2 10.8
2275
72 35.9 5.7 ----- 34.5 5.9 -----
67 35.8 5.4 6.6 5.8 5.0 4.2 - 34.4 5.8 5.7 4.9 4.1 3.3 -
62 32.0 5.0 20.5 19.7 18.9 18.1 17.3 30.1 5.1 19.9 19.1 18.3 17.4 16.6
57 31.9 5.0 23.6 23.4 22.6 21.8 21.0 30.4 5.0 21.8 21.6 20.8 20.0 19.2
2600
72 36.7 5.7 ----- 35.6 6.0 -----
67 36.6 5.4 9.2 8.1 6.9 5.7 - 35.5 5.9 8.5 7.2 6.0 4.7 -
62 32.7 5.0 28.7 27.5 26.3 25.2 24.0 31.0 5.2 28.8 27.5 26.3 25.0 23.8
57 32.6 5.0 32.6 32.6 31.4 30.3 29.1 31.3 5.2 31.3 31.3 30.1 28.8 27.6
2925
72 37.0 5.6 ----- 35.9 5.8 -----
67 36.9 5.4 11.5 10.2 8.8 7.4 - 35.8 5.8 10.9 9.4 7.9 6.4 -
62 33.0 4.9 30.9 30.4 29.0 27.6 26.2 31.3 5.0 30.2 29.6 28.0 26.5 25.0
57 32.8 4.9 32.8 32.8 31.5 30.1 28.7 31.6 5.0 31.6 31.6 30.1 28.6 27.1
3250
72 37.2 5.6 ----- 36.2 5.7 -----
67 37.1 5.3 13.9 12.3 10.7 9.1 - 36.1 5.6 13.3 11.5 9.8 8.0 -
62 33.2 4.9 33.2 33.2 31.6 30.0 28.4 31.6 4.9 31.6 31.6 29.8 28.1 26.3
57 33.1 4.9 33.1 33.1 31.5 29.9 28.3 31.9 4.9 31.9 31.9 30.1 28.4 26.6
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR078 (6.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
85 80 75 70 65 85 80 75 70 65