York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
52 Johnson Controls Unitary Products
115°F 125°F
750
77 32.6 3.1 11.2 9.9 7.0 - - - 28.3 3.3 9.2 7.9 5.4 - - -
72 29.2 3.0 17.7 14.8 11.8 8.9 - - 25.6 3.2 16.0 13.2 10.3 7.5 - -
67 25.9 2.9 24.2 19.6 16.6 13.7 10.8 - 22.9 3.1 22.9 18.1 15.3 12.4 9.6 -
62 22.2 2.8 22.2 22.2 20.3 17.4 14.4 11.5 19.5 3.0 19.5 19.5 19.5 16.0 13.1 10.3
900
77 34.0 3.1 14.9 11.4 7.9 - - - 29.4 3.4 13.4 9.6 6.2 - - -
72 30.5 3.0 20.4 16.9 13.4 9.9 - - 26.5 3.2 18.6 15.2 11.8 8.4 - -
67 27.0 2.9 25.9 22.4 18.9 15.4 11.9 - 23.7 3.1 23.7 20.8 17.4 14.0 10.6 -
62 23.1 2.8 23.1 23.1 23.0 19.5 16.0 12.5 20.2 3.0 20.2 20.2 20.2 18.0 14.7 11.3
57 22.8 2.8 22.8 22.8 21.2 17.8 14.3 10.8 20.0 3.1 20.0 20.0 18.8 15.5 12.1 8.7
1050
77 35.4 3.1 18.7 12.9 8.9 - - - 30.4 3.4 17.6 11.3 7.0 - - -
72 31.8 3.0 23.1 19.1 15.0 10.9 - - 27.5 3.3 21.1 17.2 13.2 9.3 - -
67 28.1 2.9 27.5 25.2 21.1 17.0 13.0 - 24.5 3.1 24.5 23.4 19.5 15.6 11.7 -
62 24.1 2.8 24.1 24.1 25.7 21.7 17.6 13.6 20.9 3.0 20.9 20.9 20.9 20.1 16.2 12.2
57 23.7 2.9 23.7 23.7 23.8 19.7 15.6 11.6 20.7 3.1 20.7 20.7 20.7 17.2 13.3 9.4
1200
77 36.8 3.1 22.4 14.5 9.8 - - - 31.4 3.4 21.9 12.9 7.7 - - -
72 33.0 3.0 25.8 21.2 16.6 12.0 - - 28.4 3.3 23.6 19.1 14.7 10.2 - -
67 29.2 2.9 29.2 28.0 23.3 18.7 14.1 - 25.4 3.1 25.4 25.4 21.6 17.2 12.7 -
62 25.0 2.8 25.0 25.0 28.5 23.8 19.2 14.6 21.6 3.0 21.6 21.6 21.6 21.6 17.7 13.2
57 24.7 2.9 24.7 24.7 26.3 21.6 17.0 12.4 21.4 3.1 21.4 21.4 21.4 19.0 14.5 10.0
1350
72 33.4 3.0 28.2 23.0 17.9 12.7 - - 28.6 3.3 25.9 20.9 15.9 10.9 - -
67 29.6 2.9 29.6 28.9 25.2 20.0 14.9 - 25.6 3.2 25.6 25.6 23.4 18.4 13.4 -
62 25.3 2.9 25.3 25.3 27.0 21.9 16.7 11.6 21.8 3.1 21.8 21.8 21.8 19.3 14.3 9.3
57 24.9 2.9 24.9 24.9 25.7 20.6 15.4 10.3 21.6 3.1 21.6 21.6 21.6 17.6 12.6 7.6
1500
72 33.8 3.1 30.5 24.8 19.2 13.5 - - 28.9 3.3 28.1 22.6 17.0 11.5 - -
67 29.9 3.0 29.9 29.9 27.0 21.3 15.6 - 25.8 3.2 25.8 25.8 25.1 19.6 14.0 -
62 25.6 2.9 25.6 25.6 25.6 19.9 14.3 8.6 22.0 3.1 22.0 22.0 22.0 16.4 10.9 5.4
57 25.2 2.9 25.2 25.2 25.2 19.6 13.9 8.2 21.8 3.2 21.8 21.8 21.8 16.2 10.7 5.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ037 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65