York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
68 Johnson Controls Unitary Products
115°F 125°F
750
77 34.0 2.4 11.6 10.9 8.1 - - - 31.5 2.1 11.5 9.9 7.9 - - -
72 30.0 2.5 18.1 15.3 12.4 9.6 - - 27.2 2.3 17.2 14.5 11.7 9.0 - -
67 26.0 2.6 24.6 19.6 16.8 13.9 11.1 - 22.8 2.6 22.8 18.3 15.6 12.9 10.1 -
62 22.8 2.4 22.8 22.8 18.0 15.1 12.3 9.5 20.5 2.2 20.5 20.5 16.5 13.7 11.0 8.3
900
77 34.5 2.5 15.9 12.4 9.0 - - - 31.4 2.3 15.9 11.8 8.5 - - -
72 30.4 2.6 20.7 17.2 13.8 10.3 - - 27.1 2.5 19.3 16.0 12.7 9.3 - -
67 26.4 2.7 25.5 22.0 18.6 15.1 11.7 - 22.7 2.8 22.7 20.1 16.8 13.5 10.2 -
62 23.1 2.5 23.1 23.1 19.9 16.5 13.0 9.6 20.4 2.4 20.4 20.4 17.7 14.4 11.1 7.7
57 23.7 2.5 23.7 23.7 20.4 17.0 13.5 10.1 22.5 2.5 22.5 22.5 19.5 16.2 12.8 9.5
1050
77 35.0 2.6 20.1 13.9 9.8 - - - 31.3 2.5 20.3 13.7 9.2 - - -
72 30.9 2.7 23.2 19.2 15.1 11.0 - - 26.9 2.8 21.4 17.5 13.6 9.7 - -
67 26.8 2.8 26.3 24.4 20.4 16.3 12.2 - 22.6 3.0 22.6 21.9 18.0 14.1 10.2 -
62 23.4 2.6 23.4 23.4 21.8 17.8 13.7 9.6 20.3 2.6 20.3 20.3 19.0 15.0 11.1 7.2
57 24.0 2.6 24.0 24.0 22.4 18.3 14.3 10.2 22.5 2.7 22.5 22.5 21.0 17.0 13.1 9.2
1200
77 35.4 2.7 24.4 15.4 10.7 - - - 31.2 2.7 24.7 15.6 9.8 - - -
72 31.3 2.8 25.8 21.1 16.4 11.8 - - 26.8 3.0 23.6 19.0 14.5 10.0 - -
67 27.2 2.9 27.2 26.9 22.2 17.5 12.8 - 22.4 3.3 22.4 22.4 19.2 14.7 10.2 -
62 23.8 2.7 23.8 23.8 23.8 19.1 14.4 9.7 20.2 2.8 20.2 20.2 20.2 15.7 11.2 6.7
57 24.4 2.7 24.4 24.4 24.4 19.7 15.0 10.3 22.4 2.9 22.4 22.4 22.4 17.9 13.4 8.9
1350
72 31.5 2.7 28.4 23.1 17.9 12.6 - - 27.1 2.9 26.5 21.4 16.3 11.2 - -
67 27.3 2.9 27.3 27.1 24.1 18.8 13.6 - 22.7 3.1 22.7 22.7 21.6 16.5 11.4 -
62 23.9 2.6 23.9 23.9 23.9 18.6 13.3 8.1 20.5 2.7 20.5 20.5 20.5 15.4 10.3 5.2
57 24.5 2.6 24.5 24.5 24.5 19.2 14.0 8.7 22.7 2.8 22.7 22.7 22.7 17.6 12.5 7.4
1500
72 31.6 2.7 31.1 25.2 19.3 13.4 - - 27.4 2.7 27.4 23.7 18.0 12.3 - -
67 27.4 2.8 27.4 27.4 26.0 20.2 14.3 - 23.0 3.0 23.0 23.0 23.0 18.2 12.6 -
62 24.0 2.5 24.0 24.0 24.0 18.1 12.3 6.4 20.7 2.6 20.7 20.7 20.7 15.0 9.3 3.7
57 24.6 2.5 24.6 24.6 24.6 18.8 12.9 7.0 22.9 2.7 22.9 22.9 22.9 17.2 11.5 5.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR037 (3.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65