York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
58 Johnson Controls Unitary Products
115°F 125°F
1625
77 72.1 6.8 27.6 25.3 18.8 - - - 63.3 7.3 26.5 21.1 16.1 - - -
72 64.6 6.6 41.6 35.1 28.6 22.1 - - 56.2 7.1 37.8 31.6 25.4 19.2 - -
67 57.2 6.4 55.6 44.9 38.4 31.9 25.4 - 49.1 6.9 49.1 40.9 34.7 28.5 22.3 -
62 50.7 6.3 50.7 50.7 42.5 36.0 29.5 23.0 43.2 6.8 43.2 43.2 37.2 31.0 24.8 18.6
1950
77 75.3 6.8 36.7 28.9 21.1 - - - 66.8 7.4 36.3 25.9 18.4 - - -
72 67.5 6.6 47.7 39.9 32.1 24.3 - - 59.3 7.2 44.1 36.5 29.0 21.4 - -
67 59.8 6.5 58.7 50.9 43.1 35.3 27.5 - 51.8 7.0 51.8 47.1 39.6 32.1 24.5 -
62 53.0 6.4 53.0 53.0 47.8 40.0 32.2 24.4 45.6 6.8 45.6 45.6 42.5 34.9 27.4 19.8
57 56.6 6.4 56.6 56.6 49.6 41.8 34.0 26.2 52.3 6.9 52.3 52.3 43.4 35.9 28.4 20.8
2275
77 78.5 6.8 45.8 32.5 23.4 - - - 70.2 7.4 46.1 30.7 20.7 - - -
72 70.4 6.7 53.8 44.7 35.6 26.6 - - 62.4 7.2 50.3 41.5 32.6 23.7 - -
67 62.3 6.5 61.8 56.9 47.8 38.8 29.7 - 54.6 7.0 54.6 53.4 44.5 35.6 26.7 -
62 55.3 6.4 55.3 55.3 53.0 43.9 34.9 25.8 48.0 6.8 48.0 48.0 47.8 38.9 30.0 21.1
57 59.1 6.4 59.1 59.1 55.0 46.0 36.9 27.8 55.0 6.9 55.0 55.0 48.9 40.0 31.1 22.2
2600
77 81.7 6.9 54.9 36.1 25.7 - - - 73.7 7.5 56.0 35.5 23.0 - - -
72 73.3 6.7 59.9 49.5 39.2 28.8 - - 65.5 7.2 56.6 46.4 36.2 25.9 - -
67 64.9 6.6 64.9 62.9 52.6 42.2 31.9 - 57.3 7.0 57.3 57.3 49.4 39.1 28.9 -
62 57.5 6.4 57.5 57.5 58.3 47.9 37.5 27.2 50.4 6.9 50.4 50.4 50.4 42.8 32.6 22.3
57 61.5 6.5 61.5 61.5 60.5 50.1 39.7 29.4 57.6 7.0 57.6 57.6 54.3 44.1 33.8 23.6
2925
72 74.5 6.7 63.6 52.5 41.4 30.3 - - 66.4 7.3 59.9 49.0 38.1 27.2 - -
67 65.9 6.6 65.9 65.0 55.6 44.5 33.4 - 58.0 7.1 58.0 58.0 52.0 41.1 30.2 -
62 58.5 6.5 58.5 58.5 58.8 47.7 36.6 25.5 51.1 6.9 51.1 51.1 51.1 41.5 30.6 19.6
57 62.5 6.5 62.5 62.5 62.0 50.9 39.8 28.7 58.4 7.0 58.4 58.4 56.8 45.8 34.9 24.0
3250
72 75.7 6.8 67.3 55.4 43.6 31.8 - - 67.2 7.3 63.2 51.6 40.0 28.4 - -
67 67.0 6.6 67.0 67.0 58.5 46.7 34.9 - 58.8 7.1 58.8 58.8 54.7 43.1 31.5 -
62 59.4 6.5 59.4 59.4 59.4 47.6 35.8 23.9 51.7 7.0 51.7 51.7 51.7 40.1 28.5 16.9
57 63.5 6.5 63.5 63.5 63.5 51.7 39.8 28.0 59.2 7.1 59.2 59.2 59.2 47.6 36.0 24.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65