York R-410A ZH/ZJ/ZR Series Air Conditioner User Manual


 
528150-YTG-G-1210
74 Johnson Controls Unitary Products
115°F 125°F
1250
77 60.8 6.1 19.8 18.1 13.3 - - - 55.9 7.3 18.9 12.5 10.1 - - -
72 52.8 5.6 32.2 26.9 21.6 16.2 - - 47.8 6.5 29.2 24.0 18.8 13.6 - -
67 44.7 5.0 44.7 35.7 29.8 24.5 19.1 - 39.6 5.7 39.6 34.3 27.5 22.3 17.1 -
62 37.9 5.3 37.9 37.9 30.0 24.7 19.4 14.0 32.9 5.9 32.9 32.9 24.3 19.1 13.9 8.7
1500
77 61.3 5.9 27.6 20.9 14.6 - - - 55.4 7.0 27.2 17.4 11.1 - - -
72 53.2 5.4 36.3 30.0 23.6 17.3 - - 47.3 6.2 33.2 27.0 20.7 14.4 - -
67 45.0 4.8 45.0 39.0 32.7 26.4 20.0 - 39.2 5.4 39.2 36.5 30.3 24.0 17.8 -
62 38.2 5.1 38.2 38.2 32.9 26.6 20.3 14.0 32.5 5.7 32.5 32.5 26.8 20.5 14.3 8.0
57 40.1 5.2 40.1 40.1 34.6 28.3 22.0 15.6 35.4 5.8 35.4 35.4 29.3 23.0 16.8 10.5
1750
77 61.7 5.7 35.4 23.8 15.9 - - - 54.8 6.7 35.6 22.3 12.2 - - -
72 53.5 5.2 40.4 33.1 25.7 18.4 - - 46.8 5.9 37.2 29.9 22.6 15.3 - -
67 45.3 4.7 45.3 42.3 35.6 28.3 20.9 - 38.8 5.2 38.8 38.8 33.0 25.7 18.4 -
62 38.5 4.9 38.5 38.5 35.8 28.5 21.2 13.9 32.1 5.4 32.1 32.1 29.2 21.9 14.7 7.4
57 40.4 5.0 40.4 40.4 37.7 30.3 23.0 15.7 35.0 5.5 35.0 35.0 31.9 24.7 17.4 10.1
2000
77 62.2 5.5 43.2 26.6 17.2 - - - 54.3 6.4 43.9 27.2 13.2 - - -
72 53.9 5.0 44.4 36.1 27.8 19.5 - - 46.3 5.7 41.1 32.8 24.5 16.1 - -
67 45.7 4.5 45.7 45.7 38.5 30.1 21.8 - 38.3 4.9 38.3 38.3 35.7 27.4 19.1 -
62 38.8 4.8 38.8 38.8 38.8 30.4 22.1 13.8 31.7 5.1 31.7 31.7 31.7 23.4 15.0 6.7
57 40.7 4.8 40.7 40.7 40.7 32.4 24.1 15.8 34.6 5.2 34.6 34.6 34.6 26.3 18.0 9.6
2250
72 53.9 5.2 48.1 38.9 29.8 20.7 - - 46.2 5.9 44.6 35.4 26.3 17.1 - -
67 45.6 4.7 45.6 45.6 41.2 32.1 23.0 - 38.2 5.1 38.2 38.2 38.2 29.3 20.1 -
62 38.7 5.0 38.7 38.7 38.7 29.6 20.5 11.4 31.6 5.4 31.6 31.6 31.6 22.4 13.3 4.1
57 40.7 5.1 40.7 40.7 40.7 31.6 22.5 13.4 34.5 5.5 34.5 34.5 34.5 25.3 16.2 7.1
2500
72 53.8 5.5 51.7 41.8 31.9 22.0 - - 46.0 6.1 46.0 38.1 28.1 18.2 - -
67 45.6 4.9 45.6 45.6 44.0 34.1 24.2 - 38.1 5.3 38.1 38.1 38.1 31.1 21.2 -
62 38.7 5.2 38.7 38.7 38.7 28.8 18.9 9.0 31.5 5.6 31.5 31.5 31.5 21.5 11.5 1.6
57 40.6 5.3 40.6 40.6 40.6 30.7 20.8 10.9 34.4 5.7 34.4 34.4 34.4 24.4 14.5 4.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR061 (5.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65