Vista N7227V5 Home Security System User Manual


 
TO DETERMINE
TOTAL STANDBY
LOAD ON BATTERY,
ADD 100mA TO
TOTAL OF AUX.
POWER OUTPUT
AND REMOTE
KEYPAD
CURRENTS.
USE UL LISTED
LIMITED ENERGY
CABLE FOR
CONNECTIONS
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE
ALARM HEADQUARTERS OR A CENTRAL STATION SHALL
BE PERMITTED ONLY WITH THE PERMISSION OF THE
LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE
EMERGENCY NUMBER.
1 2 3 4 5 6 7 8 9 1011121314151617181920 21
LOCATED AT
LOWER RIGHT
OF CIRCUIT
BOARD
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X* JACK DIRECT
CONNECT CORD)
*in CANADA, CA38A JACK
DOC LOAD NO.: 3
REMOTE KEYPADS
SYSTEM MUST BE
PROGRAMMED WITH A
6139 KEYPAD. IT NEED
NOT REMAIN IN SYSTEM
AFTER PROGRAMMING.
THE SYSTEM CAN USE:
6127 (20mA), 6128 (30mA),
6137 (85mA), 6138 (100mA),
OR 6139 (100mA).
MULTIPLE KEYPADS MAY BE
USED, BUT USE MAX. OF
220 FT. OF #22 WIRE, OR
550 FT. OF #18 WIRE.
BLACK: KEYPAD GROUND () RETURN
RED: KEYPAD PWR (+)
GREEN: DATA IN FROM KEYPAD
YELLOW: DATA OUT TO KEYPAD
REMOTE
KEYPAD(S)
}
SEALED LEAD ACID TYPE
BATTERY. NORMALLY
NEED NOT BE
REPLACED FOR AT
LEAST 3 YRS.
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 72,
CHAPTER 2 (NATIONAL FIRE PROTECTION
ASSOC., BATTERYMARCH PARK, QUINCY,
MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
CHARGING
VOLTAGE
13.8VDC
BATTERY
12V, 4AH
+
+
CONNECTOR
TABS
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO 1321.
USE 1321CN
in CANDA)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
+
BATTERY FUSE
(e.g. ADEMCO No. 90-12)
FOR REPLACEMENT
USE SAME VALUE
3A
BLK
RED
GRN
YEL
FOR UP TO 16 RF EXPANSION ZONES
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 5
ZONE 6
HI
LO
HI
LO
WARNING:
OWNER'S INSTRUCTION NOTICE NOT
TO BE REMOVED. WEEKLY TESTING IS REQUIRED TO
ENSURE PROPER OPERATION OF THIS SYSTEM.
TIP
(BROWN)
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
}
}
INCOMING
PHONE
LINE
HANDSET
BLACK
RED
+
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 1
ZONE 2
HI
LO
HI
LO
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 3
ZONE 4
HI
LO
HI
LO
• MAXIMUM LOOP RESISTANCE (EACH ZONE) 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 1-6: 300-500MSEC
• ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR
FAST RESPONSE TO AN OPEN: 10MSEC MAX
• ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE.
ADEMCO 5881* Type
RF RECEIVER
WIRELESS ZONES
5881L:
UP TO 8
5881M/5881H/5881EH: UP TO 16
*
5882 Type in CANADA
ADEMCO No. 4204
RELAY MODULE (180mA MAX)
(4 OUTPUT RELAYS)
SET UNITS DIP SWITCH
FOR DEVICE ADDRESS OF 0
(See receivers instructions)
SET UNITS DIP SWITCH
FOR DEVICE ADDRESS OF 1
(See units instructions)
THESE OPTIONAL ITEMS
MAY ALSO BE USED
SEE THEIR INSTRUCTIONS
ADEMCO 5800TM
TRANSMITTER MODULE
(20mA)
(for 5827BD Wireless
Bi-directional Keypad)
AND/OR
ADEMCO 4285/4286
VIP MODULE 160mA/300mA
AND/OR
ADEMCO ECP COMPATIBLE
LONG RANGE RADIO
OPTIONAL
24 HR BATTERY STANDBY REQUIRED
FOR FIRE INSTALLATIONS. USE 12V,
17.2AH BATTERY FOR 500mA AUX
POWER. SEE INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4
HOURS.
FOR
COMPLETE
INFORMATION,
SEE
INSTRUCTIONS
N7227V5
RED
JUMPER
CUT FOR BELL SUPERVISION.
ALSO CONNECT A 1000 OHM
EOLR ACROSS SOUNDER
AUX. POWER
OUTPUT
10.5-13.8VDC
500mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET.
ALL CIRCUITS
ARE POWER
LIMITED.
NOTE:
KEYPAD
CURRENT
MUST BE
INCLUDED
IN AUX.
CURRENT
DRAIN
CALCULA-
TIONS
ALARM OUTPUT
10.5-13.8VDC, 2A MAX.
(600mA MAX. FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL
SOUNDING FOR FIRE (e.g. USE ADEMCO 740
SOUNDER, 702 OR 719 SIREN, OR 12V BELL)
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
+
1000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
+
BLK
+
V10SE-032-V0
WARNING:
TO PREVENT RISK OF SHOCK, DISCONNECT
TELEPHONE LINE AT TELCO JACK BEFORE
SERVICING THIS UNIT.
Figure 17. VISTA10SE SUMMARY OF CONNECTIONS DIAGRAM