Table M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data
Water-Cooled Units Air-Cooled Units
Unit Size 20 25 30 35 20 25 32
Compressor Data
Quantity 2 2 1/1 2 2 1/1 2
Nominal Ton/Comp 10 10 10/15 15 10 10/15 15
Circuits 2 2 2 2 2 2 2
Evaporator Coil Data
Rows 2 4 4 4 3 4 4
Sq. Ft. 22.5 25.0 25.0 25.0 25.0 25.0 25.0
FPF 144 144 144 144 144 144 144
Condenser Data
Minium GPM w/o Econ 36 36 46 54
Minimum GPM w/ Econ 41 41 60 65
Maximum GPM 80 80 102 119
Evaporator Fan Data
Quantity 2 2 2 2 2 2 2
Size (Dia. x width - inches) 12
5
/
8
”x8" 12
5
/
8
”x9" 12
5
/
8
”x11" 12
5
/
8
x11" 12
5
/
8
”x8" 12
5
/
8
”x9" 12
5
/
8
”x11"
Minimum HP 5 5 5 5 5 5 5
Maximum HP 20 25 25 25 20 25 25
Minimum Design CFM 6350 7250 7250 7250 7250 7250 7250
Maximum Design CFM 8500 10,625 12,750 14,875 8500 10,625 13600
R-22 Refrigerant Data
EER 12.6 13.9 13.4 12.5 10.3 10.7 10.1
IPLV 13.2 14.1 12.9 12.2 11.4 11.4 10.4
Refrigerant Charge - lbs.
Circuit A 25 25 27 27
Circuit B 25 25 25 27
Capacity Steps - % 100/53/0 100/53/0 100/65/47/0 100/53/0 100/52/0 100/66/47/0 100/52/0
407C Refrigerant Data
EER 11.6 13.2 12.3 11.3
IPLV 12.3 13.5 12.2 11.5
Refrigerant Charge - lbs
Circuit A 23.5 23.5 26.5 26.5
Circuit B 23.5 23.5 23.5 26.5
Capacity Steps - % 100/53/0 100/53/0 100/65/42/6 100/53/0
Filter Data
Quantity 4 4 4 4 4 4 4
Size (inches) (16x25x2) (16x25x2) (16x25x2) (16x25x2) 16x25x2 16x25x2 16x25x2
Quantity 4 4 4 4 4 4 4
Size (inches) 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2
CCRC/CIRC Condenser Match 20 29 32
Notes:
1. Compressors are Trane 3D
®
scroll.
2.EER and IPLV are rated in accordance to the ARI Standard 340/360-93 for large unitary equipment. Based on 80/67°F (26.7/19.4°C) to the evaporator coil, nominal airflow and 85-95°F (29.4-
35°C) condenser water.
3. All units operate with R-22. Units ships with full operating charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Filter sizes are for units without hot water or steam heating coils
Table M-GI-2. SCWG/SIWG/SCRG/SIRG Self-Contained Heating Coil Maintenance Data
Filter Data for Heating Coil
Quantity 4
Size (inches) 20x18x2
Size (mm) (508x457x51)
Quantity 8
Size (inches) 20x20x2
Size (mm) (508x508x51)
Coil Data Type Rows No. - Size (in) No. - Size (mm) fpf
Steam Coil NS 1 2 - 24 x 58 2 - 609.6x1473.2 42
Hot Water Coil WC 1 2 - 24 x 58 2 - 609.6x1473.2 80
Notes: 1. Hot water and steam heating coils have Prima-Flo
®
fins and do not have turbulators. 2. For coil capacities, use TOPSS
(Trane Official
Product Selection Program). 3. Full capacity coils consist of two coils stacked and piped in parallel.
Maintenance
general
information