Trane SCXG-SVX01B-EN Air Conditioner User Manual


 
SCXG-SVX01B-EN 29
VFD
Dimensions &
Weights
Variable Frequency Drive with Bypass
VFD with bypass dimensions, in.
voltage hp A B C D E F G H
460 7.5 30.40 28.03 16.14 23.35 24.85 0.75 8.59 10.63
10
208 7.5 41.28 38.89 16.14 24.00 25.5 0.75 10.95 12.99
10
15
20
460 15
20
25
208 25 50.81 48.35 21.36 31.61 33.41 0.90 12.36 14.41
H
G
E
D
F
B
A
C
Electrical Installation Procedure
Refer to the
National Electric Code,
section 310-16
for sizing wires 4B - 9B. All
other control wires should be twisted
shielded or twisted pair shielded, 20 - 14
AWG, with lead length not to exceed 164
feet. When using shielded wire, the shield
sheath must be connected at the VFD
only. The connection on units with VFD is
J13-S. The connection on unis with VFD/
bypass is ITBI-10.