14 SCXG-SVX01B-EN
pre-installation
considerations
Installation
Rigging and Unit Handling
ƽƽ
ƽƽ
ƽWARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to
verify proper center of gravity lift point.
To avoid dropping of unit, reposition
lifting point if unit is not level. Failure to
properly lift unit could result in death or
serious injury or possible equipment or
property-only damage.
ƽƽ
ƽƽ
ƽWARNING
Lifting Equipment Capacity!
Ensure lifting equipment capacity
exceeds unit weight by an adequate
safety factor to prevent injury, death, or
unit damage.
Figure I-PC-5. Assembled unit gravity block location.
Table I-PC-2. Gravity Block Dimensions
Model A B C D
SCWG 36 14 38 12
SCRG 36 16 40 12
Fan Section Only
Compressor Section Only
Before lifting the unit or modular
component, determine the approximate
center of gravity for lifting safety. See
Figure I-PC-5 for assembled modular
units and Figure I -PC-6 for split-apart
units. The center of gravity may vary
slightly within the gravity block
depending on unit options.
Always test-lift the unit to determine the
exact unit balance and stability before
hoisting it to the installation location. See
Figures I-PC-7 and I-PC-8 for typical
rigging procedures and proper rigging
equipment usage.
Figure I-PC-6. Split-apart unit gravity block location.