Trane SCXG-SVX01B-EN Air Conditioner User Manual


 
36 SCXG-SVX01B-EN
pre-startup
requirements
Plenum
Before installing the plenum attach the
insulation strip that ships with the plenum.
See Figure I-PR-3 for proper insulation
location. Align the plenum front with the
control panel side of the unit. Using the
strips and screws provided, secure the
plenum to the unit.
Treat field-cut holes to prevent fiberglass
from entering the airstream.
Note: Plenum insulation must be applied
properly to prevent air bypass around the
plenum. See Figure I-PR-3.
Figure I-PR-3. Correct plenum insulation placement
Plenum Bottom View
Dashed line indicates correct insulation placement.
Installation