Toshiba HFC R-410A Air Conditioner User Manual


 
58
Outdoor units
Rating hp 5 6 8 10 12
Cooling only model MMY MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8
Heat pump model MMY MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8
Outdoor unit type Inverter Inverter Inverter Inverter Inverter
Cooling capacity kW 14.0 16.0 22.4 28.0 33.5
Heating capacity kW 16.0 18.0 25.0 31.5 37.5
Power supply V-ph-Hz 400-3-50 ± 10% 400-3-50 ± 10% 400-3-50 ± 10% 400-3-50 ± 10% 400-3-50 ± 10%
Voltage range V 380-415 380-415 380-415 380-415 380-415
Power input, cooling kW 3.65 4.64 5.67 7.68 11.92
Power factor, cooling % 90 92 95 96 94
Operating current, cooling A 5.85 7.28 8.62 11.55 18.30
EER, cooling kW/kW 3.84 3.45 3.95 3.65 2.81
Starting current A 1.0 1.0 1.0 1.0 1.0
Power input, heating kW 3.84 4.56 5.88 7.97 10.19
Power factor, heating % 91 93 95 96 94
Operating current, heating A 6.09 7.08 8.93 11.98 15.65
COP, heating kW/kW 4.17 3.95 4.25 3.95 3.68
Starting current A 1.0 1.0 1.0 1.0 1.0
Unit appearance Silky shade (Munsell 1Y8.5/0.5)
Dimensions
Height mm 1800 1800 1800 1800 1800
Width mm 990 990 990 990 990
Depth mm 750 750 750 750 750
Total weight - cooling only unit kg 227 227 256 256 256
Total weight - heat pump unit kg 228 228 258 258 258
Heat exchanger Finned type
Sound power level dB(A) 68 69 70 71 72
Sound pressure leve
l dB(A) at 1 m 55 56 57 58 59
Fan type Propeller Propeller Propeller Propeller Propeller
Motor power input kW 0.6 0.6 0.6 0.6 0.6
Air flow l/s - m
3
/h 2500 - 9000 2500 - 9000 2750 - 9900 2917 - 10500 2917 - 10500
Compressor type Hermetic Hermetic Hermetic Hermetic Hermetic
Motor power input kW 1.1 x 2 1.4 x 2 2.3 x 2 3.1 x 2 4.2 x 2
Refrigerant charge R-410A*
Cooling kg 8.0 8.0 11.0 11.0 11.0
Heating kg 8.5 8.5 12.5 12.5 12.5
Pipework**
Suction line type - diameter in Flare - 5/8 Brazed - 3/4 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8
Liquid line type - diameter in Flare - 3/8 Flare - 3/8 Flare - 1/2 Flare - 1/2 Flare - 1/2
Balance pipe type - diameter in Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8
Maximum equivalent length separation m 175 175 175 175 175
Maximum actual piping length m 150 (if equivalent bend length is longer, equivalent length is standard)
Maximum total piping length m 300 300 300 300 300
Maximum lift - indoor unit above/below*** m 40/50 40/50 40/50 40/50 40/50
Control wiring Shielded wire 1.25 mm
2
x 2 cores up to 2000 m
Central remote controller Shielded wire 1.25 mm
2
x 2 pieces up to 1000 m, 2.0 mm
2
x 2 pieces up to 2000 m
Max. number of connectable indoor units 8 10 13 16 20
High-pressure switch MPa Off: 2.90/On: 3.73
Protection devices Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
Operating range, cooling† °C -5 to 43 db -5 to 43 db -5 to 43 db -5 to 43 db -5 to 43 db
Operating range, heating† °C -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
* The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.