High-wall units (2 Series)
Model MMK-AP 0072H 0092H 0122H
Cooling capacity* kW 2,2 2,8 3,6
Heating capacity kW 2,5 3,2 4,0
Electrical data
Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current A 0,17 0,18 0,19
Power input kW 0,017 0,018 0,019
Starting current A 0,22 0,23 0,24
Unit appearance
Suction grille and side panel Moon white
Discharge grille Moon white
Bottom surface Moon white
Unit dimensions
Height mm 275 275 275
Width mm 790 790 790
Depth mm 208 208 208
Unit weight kg 11 11 11
Heat exchanger Finned tube
Sound proofing/heat insulating material Non-flammable insulation
Fan type Tangential fan
Fan motor power input W 30 30 30
Air flow
High l/s 133 142 150
Medium l/s 117 125 125
Low l/s 100 100 100
Air flow
High m
3
/h 480 510 540
Medium m
3
/h 420 450 450
Low m
3
/h 360 360 360
Sound power level (high/medium/low) dB(A) 48/45/42 49/46/42 50/46/42
Sound pressure level
(high/medium/low)** dB(A) 35/32/29 36/33/29 37/33/29
Air filter Standard single filter supplied
Controller Remote controller
Connection pipes
Gas connection diameter in 3/8 3/8 3/8
Liquid connection diameter in 1/4 1/4 1/4
Drain connection, nom. dia (polyvinyl tube) mm 16 16 16
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
* Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
** The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.