49
Indoor units
Standard ducted units
Model MMD-AP 0071BH 0091BH 0121BH 0151BH 0181BH 0241BH 0271BH 0301BH 0361BH 0481BH 0561BH
Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0
Electrical data
Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current A 0.29 0.29 0.34 0.34 0.43 0.52 0.52 0.61 0.83 0.98 0.98
Power input kW 0.033 0.033 0.039 0.039 0.050 0.060 0.060 0.071 0.107 0.128 0.128
Starting current A 0.50 0.50 0.59 0.59 0.75 0.90 0.90 1.05 1.44 1.70 1.70
Unit appearance Zinc hot dipping steel plate
Unit dimensions
Height mm 320 320 320 320 320 320 320 320 320 320 320
Width mm 550 550 550 700 700 1000 1000 1000 1350 1350 1350
Depth mm 800 800 800 800 800 800 800 800 800 800 800
Unit weight kg 28 28 28 32 32 43 43 43 55 55 55
Heat exchanger Finned tube
Sound proofing/heat insulating material Non-flammable insulation
Fan type Centrifugal fan
Fan motor power input W 120 120 120 120 120 120 120 120 120 120 120
Air flow
High l/s 133 133 158 181 217 317 317 350 450 550 550
Medium l/s 117 117 136 150 183 275 275 300 392 475 475
Low l/s 95 95 111 133 150 242 242 242 333 414 414
Air flow
High m
3
/h 480 480 570 650 780 1140 1140 1260 1620 1980 1980
Medium m
3
/h 420 420 490 540 660 990 990 1080 1410 1710 1710
Low m
3
/h 340 340 400 480 540 870 870 870 1200 1490 1490
Static pressure (factory setting) Pa 40 40 40 40 40 40 40 40 40 40 40
Static pressure (max.) Pa 100 100 100 100 100 100 100 100 100 100 100
Sound power level (high/medium/low) dB(A) 43/41/39 43/41/39 44/42/40 44/42/40 45/43/41 46/44/42 46/44/42 47/45/42 49/47/45 51/49/45 51/49/45
Sound pressure level (high/medium/low)** dB(A) 30/28/26 30/28/26 31/29/27 31/29/27 32/30/28 33/31/29 33/31/29 34/32/29 36/34/32 38/36/32 38/36/32
Air filter Standard long-life filter supplied
Controller Remote controller
Connection pipes
Gas connection diameter in 3/8 3/8 3/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8
Liquid connection diameter in 1/4 1/4 1/4 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8
Drain connection, nom. dia (polyvinyl tube) in 1 1 1 1 1 1 1 1 1 1 1
Panel dimensions
Height mm 9 9 9 9 9 9 9 9 9 9 9
Width mm 630 630 630 780 780 1080 1080 1080 1430 1430 1430
Depth mm 500 500 500 500 500 500 500 500 500 500 500
Panel weight kg 3.5 3.5 3.5 4.0 4.0 6.0 6.0 6.0 7.0 7.0 7.0
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
* Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
** The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.