Toshiba HFC R-410A Air Conditioner User Manual


 
101
Outdoor module - Two units connected
MMY-AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8,
MMY-AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8,
Legend
1. Anchor bolt pitch
2. (including feet)
3. 8-15 x 20 (slot)
All dimensions are given in mm.
Notes:
1. If there is an obstacle at the top of the outdoor unit, ensure that
the top of the outdoor unit clears the obstacle by 2000 mm.
2. Ensure that the height of obstacles around the outdoor unit
does not exced 800 mm from the bottom of the outdoor unit.
3. Draw out the field-supplied pipe to the front of the outdoor unit
horizontally, and keep 500 mm or more between the outdoor
unit and pipe if placing the pipe transversely.
4. Arrange each outdoor unitin order of its capacity
(Master unit ≥ slave unit)
Unit combination Outdoor unit combination
Master unit Slave unit
MMY-AP1401T8, AP1401HT8 MMY-MAP0801T8, MAP0801HT8 MMY-MAP0601T8, MAP0601HT8
MMY-AP1601T8, AP1601HT8 MMY-MAP0801T8, MAP0801HT8 MMY-MAP0801T8, MAP0801HT8
MMY-AP1801T8, AP1801HT8 MMY-MAP1001T8, MAP1001HT8 MMY-MAP0801T8, MAP0801HT8
MMY-AP2001T8, AP2001HT8 MMY-MAP1001T8, MAP1001HT8 MMY-MAP1001T8, MAP1001HT8
MMY-AP2211T8, AP2211HT8 MMY-MAP1201T8, MAP1201HT8 MMY-MAP1001T8, MAP1001HT8
MMY-AP2411T8, AP2411HT8 MMY-MAP1201T8, MAP1201HT8 MMY-MAP1201T8, MAP1201HT8
Front
Note 4Note 3
Note 4
Note 4
Note 4
Note 3
Front
Front
Front
Front Front
Front (For work and service)
Space required for service