Toshiba HFC R-410A Air Conditioner User Manual


 
102
Outdoor module - Three units connected
MMY- AP2201T8, AP2401T8, AP2601T8, AP2801T8, AP3001T8, AP3211T8, AP3411T8,
AP3611T8
MMY- AP2201HT8, AP2401HT8, AP2601HT8, AP2801HT8, AP3001HT8,
AP3211HT8, AP3411HT8, AP3611HT8
Notes:
1. If there is an obstacle at the top of the outdoor unit, ensure that
the top of the outdoor unit clears the obstacle by 2000 mm.
2. Ensure that the height of obstacles around the outdoor unit
does not exced 800 mm from the bottom of the outdoor unit.
3. Draw out the field-supplied pipe to the front of the outdoor unit
horizontally, and keep 500 mm or more between the outdoor
unit and pipe if placing the pipe transversely.
4. Arrange each outdoor unitin order of its capacity
(Master unit ≥ slave unit ≥ slave unit)
Legend
1. Anchor bolt pitch
2. (including feet)
3. 16-15 x 20 (slot)
All dimensions are given in mm.
Note 4
Note 3
Note 4
Note 4
Note 3
Front
Front (For work and service)
Space required for service
Front
Front
FrontFrontFront
Front
Note 4
Front
Front Front
Rear
Unit combination Outdoor unit combination
Master unit Slave unit Slave unit
MMY-AP2201T8, HT8 MMY-MAP0801T8, HT8 MMY-MAP0801T8, HT8 MMY-MAP0601T8, HT8
MMY-AP2401T8, HT8 MMY-MAP0801T8, HT8 MMY-MAP0801T8, HT8 MMY-MAP0801T8, HT8
MMY-AP2601T8, HT8 MMY-MAP1001T8, HT8 MMY-MAP0801T8, HT8 MMY-MAP0801T8, HT8
MMY-AP2801T8, HT8 MMY-MAP1001T8, HT8 MMY-MAP1001T8, HT8 MMY-MAP0801T8, HT8
MMY-AP3001T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1001T8, HT8 MMY-MAP1001T8, HT8
MMY-AP3221T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1001T8, HT8 MMY-MAP1001T8, HT8
MMY-AP3411T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1001T8, HT8
MMY-AP3611T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1201T8, HT8 MMY-MAP1201T8, HT8