Toshiba HFC R-410A Air Conditioner User Manual


 
47
Indoor units
2-way ceiling cassettes
Model MMU-AP 0071WH 0091WH 0121WH 0151WH 0181WH 0241WH 0271WH 0301WH
Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0
Electrical data
Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current A 0.31 0.31 0.31 0.32 0.32 0.46 0.46 0.47
Power input kW 0.070 0.070 0.070 0.072 0.072 0.105 0.105 0.106
Power factor % 97 97 97 97 97 99 99 98
Starting current A 0.47 0.47 0.47 0.60 0.60 0.89 0.89 0.98
Unit appearance Zinc hot dipping steel plate - heat insulating material attached
Unit dimensions
Height mm 398 398 398 398 398 398 398 398
Width mm 830 830 830 1350 1350 1350 1350 1350
Depth mm 550 550 550 550 550 550 550 550
Unit weight kg 33 33 33 44 44 48 48 48
Heat exchanger Finned tube
Sound proofing/heat insulating material Non-flammable insulation
Fan type Centrifugal fan
Fan motor power input W 53 53 53 39 39 53 53 53
Air flow
High l/s 158 158 158 217 217 317 317 350
Medium l/s 142 142 142 195 195 267 267 317
Low l/s 125 125 125 167 167 200 200 267
Air flow
High m
3
/h 570 570 570 780 780 1140 1140 1260
Medium m
3
/h 510 510 510 700 700 960 960 1140
Low m
3
/h 450 450 450 600 600 720 720 960
Sound power level (high/medium/low) dB(A) 47/45/43 47/45/43 47/45/43 48/46/43 48/46/43 51/48/46 51/48/46 53/50/47
Sound pressure level (high/medium/low)** dB(A) 34/32/30 34/32/30 34/32/30 35/33/30 35/33/30 38/35/33 38/35/33 40/37/34
Air filter Standard long-life filter supplied
Controller Remote controller
Connection pipes
Gas connection diameter in 3/8 3/8 3/8 1/2 1/2 5/8 5/8 5/8
Liquid connection diameter in 1/4 1/4 1/4 1/4 1/4 3/8 3/8 3/8
Drain connection, nom. dia (polyvinyl tube) in 1 1 1 1 1 1 1 1
Ceiling panel model number RBC-UW136PG RBC-UW266PG
Panel colour Light ivory (Munsell 10Y 9/0.5)
Panel dimensions
Height mm 8 8 8 8 8 8 8 8
Width mm 1000 1000 1000 1520 1520 1520 1520 1520
Depth mm 650 650 650 650 650 650 650 650
Panel weight kg 8 8 8 11 11 11 11 11
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
* Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
** The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.