Toshiba HFC R-410A Air Conditioner User Manual


 
55
Indoor units
Floor-mounted console units
Model MML-AP 0071H 0091H 0121H 0151H 0181H 0241H
Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0
Electrical data
Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current A 0.26 0.26 0.43 0.43 0.47 0.47
Power input kW 0.056 0.056 0.092 0.092 0.102 0.102
Power factor % 94 94 93 93 94 94
Starting current A 0.60 0.60 0.80 0.80 1.10 1.10
Unit appearance Silky shade (Munsell 1Y 8.5/0.5)
Unit dimensions
Height mm 630 630 630 630 630 630
Width mm 950 950 950 950 950 950
Depth mm 230 230 230 230 230 230
Unit weight kg 37 37 37 37 40 40
Heat exchanger Finned tube
Sound proofing/heat insulating material Non-flammable insulation
Fan type Centrifugal fan
Fan motor power input W 45 45 45 45 70 70
Air flow
High l/s 133 133 250 250 300 300
Medium l/s 117 117 217 217 258 258
Low l/s 100 100 181 181 217 217
Air flow
High m
3
/h 480 480 900 900 1080 1080
Medium m
3
/h 420 420 780 780 930 930
Low m
3
/h 360 360 650 650 780 780
Sound power level (high/medium/low) dB(A) 52/50/48 52/50/48 58/54/51 58/54/51 62/57/52 62/57/52
Sound pressure level (high/medium/low)** dB(A) 39/37/35 39/37/35 45/41/38 45/41/38 49/44/39 49/44/39
Air filter Standard single filter supplied
Controller Remote controller
Connection pipes
Gas connection diameter in 3/8 3/8 3/8 1/2 1/2 5/8
Liquid connection diameter in 1/4 1/4 1/4 1/4 1/4 3/8
Drain connection, nom. dia (polyvinyl tube) in 3/4 3/4 3/4 3/4 3/4 3/4
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
* Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
** The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.