Toshiba HFC R-410A Air Conditioner User Manual


 
57
Indoor units
Floor-mounted cabinet units
Model MMF-AP 0151H 0181H 0241H 0271H 0361H 0481H 0561H
Cooling capacity* kW 4.5 5.6 7.1 8.0 11.2 14.0 16.0
Heating capacity kW 5.0 6.3 8.0 9.0 12.5 16.0 18.0
Electrical data
Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current A 0.67 0.67 0.88 0.88 1.29 1.60 1.60
Power input kW 0.150 0.150 0.190 0.190 0.280 0.350 0.350
Power factor % 97 97 94 94 94 95 95
Starting current A 0.90 0.90 1.10 1.10 1.70 2.10 2.10
Unit appearance W: Silky shade (1Y 8.5/0.5)
Unit dimensions
Height mm 1750 1750 1750 1750 1750 1750 1750
Width mm 600 600 600 600 600 600 600
Depth mm 210 210 210 210 390 390 390
Unit weight kg 48 48 49 49 65 65 65
Heat exchanger Finned tube
Sound proofing/heat insulating material Non-flammable insulation
Fan type Centrifugal fan
Fan motor power input W 37 37 63 63 110 160 160
Air flow
High l/s 250 250 333 333 533 600 600
Medium l/s 217 217 283 283 467 517 517
Low l/s 183 183 233 233 383 433 433
Air flow
High m
3
/h 900 900 1200 1200 1920 2160 2160
Medium m
3
/h 780 780 1020 1020 1680 1860 1860
Low m
3
/h 660 660 840 840 1380 1560 1560
Sound power level (high/medium/low) dB(A) 59/56/51 59/56/51 62/58/53 62/58/53 64/61/57 67/63/59 67/63/59
Sound pressure level (high/medium/low)** dB(A) 46/43/38 46/43/38 49/45/40 49/45/40 51/48/44 54/50/46 54/50/46
Air filter Standard single filter supplied
Controller Remote controller
Connection pipes
Gas connection diameter in 1/2 1/2 5/8 5/8 5/8 5/8 5/8
Liquid connection diameter in 1/4 1/4 3/8 3/8 3/8 3/8 3/8
Drain connection, nom. dia*** in 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
* Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
** The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
*** Male screw connection one side